Page 112 - Sace Emax 2 Manual for design engineers
P. 112

ABB | SACE Emax 2
        Ekip Touch - Measurements




       1 - Standard Measurements



                               List The Standard measurements are:
                                     Parameter          Description                                     Page
                                     Instantaneous currents  Phase current and earth fault measurements in real time  110
                                     Events             List of events, status changes, alarms, recorded by the Trip unit 110
                                     Trip               List of current protection trips (TRIP)         110
                                                        History of minimum and maximum currents, recorded at a
                                     Min-Max measurements                                               112
                                                        settable interval
                                     Maintenance        CB status: contact wear and last maintenance    113
                                     Operation counters  Number of mechanical and electrical operations  113



              Instantaneous currents The instantaneous currents, available in the Measurements pages, are real time measurements of the phase
                                    and earth fault currents expressed in root mean square value; the monitor time and performance depend on
                                    the rated current defined by the Rating plug (In):
                                                               Monitor time       Normal operating    Accuracy of
                                     Measurement
                                                               (min-max)          range               value read  (1)
                                     Phase currents  (4)       0,004 ÷ 64 In      0,2 ÷ 1,2 In       1%  (3)
                                     Internal earth fault current  (2)  0,08 ÷ 64 In  0,2 ÷ 1,2 In   2 %  (3)
                                     External earth fault current  (2) (5)  0,08 ÷ 4 In  0,2 ÷ 1,2 In  2 %
                                     Residual current  (2) (5)  2 ÷ 32 A                             5 %

                                    (1)  the accuracies refer to normal operating ranges, as established by IEC 61557-12
                                    (2)  available with LSIG versions
                                    (3)  accuracies based on Ekip Touch without Class 1 Power & Energy Metering package; if the Class 1 Power &
                                    Energy Metering package is present and for all other trip unit models, check the indicated performance values
                                    from page 117
                                    (4)  the higher phase currents are also available in the Histograms, Measuring instruments and Measurement
                                    summary pages
                                    (5)  available by activating the presence of toroid S.G.R or Rc

                                    Special representations

                                                        Measurement <       Measurement <      “_ _ _” displayed:
                                     Type of measurement
                                                        min value           max value          (not available) due to
                                     Internal earth fault and   . . . .     > [64 In]          Sensors disconnected
                                     phase currents
                                     External earth fault                                      Sensor not activated
                                     current            . . . .             > [4 In sensor]    and/or disconnected
                                                                                               Sensor not activated
                                     Residual current   . . . .             > 32 A
                                                                                               and/or disconnected





















       110 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                Ekip Touch - Measurements | 1 - Standard Measurements