Page 117 - Sace Emax 2 Manual for design engineers
P. 117

Continued from the previous page                                   ABB | SACE Emax 2
                                    Special representations
                                     Type of measure-  Measurement <   Measurement <     “_ _ _” displayed:
                                     ment             min value        max value         (not available) due to
                                     Line-to-line and phase   . . . .  > [Un x 1,25]     Measurement module not
                                     voltages                                            detected
                                                                                         Measurement module not present,
                                     Line frequency   30 Hz            80 Hz
                                                                                         V < 5 V
                                     Active, reactive and                                Sensors disconnected,
                                     apparent total and   . . . .      > [Pn x 1,25]     Measurement module not present,
                                     phase power                                         V < 5 V, I < 0.03 In




                           Tripping The Measuring Measurements page adds to the range of TRIPs that Ekip Touch is able to record (page 115).
                                    The voltage, frequency or power protection that trips determines the measurements recorded the moment
                                    the trip occurs
                                                    Measurements
                                     Protection                            Notes
                                                    recorded
                                                    Currents L1, L2, L3, Ne,   Ne is available with CBs type 4P and 3P + N; U0 is
                                     Voltage
                                                    voltages U12, U23, U31, U0  available in the case of trips due to RV protection
                                                    Currents L1, L2, L3, Ne and
                                     Frequency                             Ne is available with CBs type 4P and 3P + N
                                                    grid frequency
                                                                           Ne is available with CBs type 4P and 3P + N;
                                                    Currents L1, L2, L3, Ne and
                                     Power                                 Active or apparent total power depending on which
                                                    total power
                                                                           protection tripped


         Min-Max-Med measurements The Measuring Measurements package adds to the range of measurements that Ekip Touch is able to record
                                    (page 111):
                                     •  Maximum and medium voltage
                                     •  Active, reactive and apparent maximum and medium powers
                                    The type of information given, the available commands and notes are the same as those described for the
                                    current measurements.
                                           NOTES:
                                            •  compared to the current measurements, graphic representation is with respect to 1 Un (with
                                              maximum value 1.25 Un) for the voltage recordings and with respect to 1 Sn (with maximum
                                              value 1.25 Sn) for the power recordings
                                            •  and the power measurement is negative, the color of the corresponding bar is different from
                                              those with a positive value


                        Peak factor The peak factors are real time measurements of the ratio between the peak and RMS values of the phase
                                    current; the measurement is supported by the Harmonic distortion protection function (page 61).
                                     Measurement    Monitor time    Accuracy        Notes
                                                                                    “_ _ _” (not available) is indicated
                                     Peak factor    0,3 ÷ 6In       1,5%            for currents outside the range and
                                                                                    disconnected sensors





















       115 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A            Ekip Touch - Measurements | 2 - Ekip Measuring Measurements
   112   113   114   115   116   117   118   119   120   121   122