Page 117 - Sace Emax 2 Manual for design engineers
P. 117
Continued from the previous page ABB | SACE Emax 2
Special representations
Type of measure- Measurement < Measurement < “_ _ _” displayed:
ment min value max value (not available) due to
Line-to-line and phase . . . . > [Un x 1,25] Measurement module not
voltages detected
Measurement module not present,
Line frequency 30 Hz 80 Hz
V < 5 V
Active, reactive and Sensors disconnected,
apparent total and . . . . > [Pn x 1,25] Measurement module not present,
phase power V < 5 V, I < 0.03 In
Tripping The Measuring Measurements page adds to the range of TRIPs that Ekip Touch is able to record (page 115).
The voltage, frequency or power protection that trips determines the measurements recorded the moment
the trip occurs
Measurements
Protection Notes
recorded
Currents L1, L2, L3, Ne, Ne is available with CBs type 4P and 3P + N; U0 is
Voltage
voltages U12, U23, U31, U0 available in the case of trips due to RV protection
Currents L1, L2, L3, Ne and
Frequency Ne is available with CBs type 4P and 3P + N
grid frequency
Ne is available with CBs type 4P and 3P + N;
Currents L1, L2, L3, Ne and
Power Active or apparent total power depending on which
total power
protection tripped
Min-Max-Med measurements The Measuring Measurements package adds to the range of measurements that Ekip Touch is able to record
(page 111):
• Maximum and medium voltage
• Active, reactive and apparent maximum and medium powers
The type of information given, the available commands and notes are the same as those described for the
current measurements.
NOTES:
• compared to the current measurements, graphic representation is with respect to 1 Un (with
maximum value 1.25 Un) for the voltage recordings and with respect to 1 Sn (with maximum
value 1.25 Sn) for the power recordings
• and the power measurement is negative, the color of the corresponding bar is different from
those with a positive value
Peak factor The peak factors are real time measurements of the ratio between the peak and RMS values of the phase
current; the measurement is supported by the Harmonic distortion protection function (page 61).
Measurement Monitor time Accuracy Notes
“_ _ _” (not available) is indicated
Peak factor 0,3 ÷ 6In 1,5% for currents outside the range and
disconnected sensors
115 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Ekip Touch - Measurements | 2 - Ekip Measuring Measurements