Page 116 - Sace Emax 2 Manual for design engineers
P. 116

ABB | SACE Emax 2
       2 - Ekip Measuring Measurements



                               List The Measuring measurements are
                                     Condition             Access                                       Page
                                     Instantaneous voltages  Phase and line-to-line voltage measurements in real time  114
                                                           Real time measurements of the active, reactive, apparent
                                     Instantaneous powers                                               114
                                                           phase and total powers
                                     Instantaneous frequency  Measurement of the line frequency         114
                                                           List of trips (TRIP) due to voltage, frequency, power
                                     Trip                                                               115
                                                           protections
                                                           History of minimum, maximum and mean voltages and
                                     Min-Max-Med measurements                                           115
                                                           powers recorded within a settable range
                                     Peak factor           Real time measurement of the peak factor of the currents  115
                                     Power factor          Real time measurement of the power factor    115
                                     Energy counters       Measurement of active, reactive, apparent energy  115

                                    The relative associated measurements are activated by means of the Ekip Synchrocheck module (page 223).


         Instantaneous measurements Instantaneous currents, available in the Summary pages, are real time measurements of the line-to-line and
                                    phase voltages expressed in root-mean-square value.
                                    Representation, measuring range and performance depend on the set rated voltage (Un).
                                    Available in the Summary pages, the instantaneous powers are real time measurements of the phase and
                                    total active powers.
                                    Representation, measuring range and performance depend on the set rated voltage (Un) and on the rated
                                    current defined by the rated size of the Trip unit (In); in addition, the reference changes on the basis of the
                                    type of measurement:
                                     •  Sn for total powers (Sn = In * Un * √3).
                                     •  Pn for phase powers (Pn = In * Un / √3).
                                           NOTE: the phase powers and voltages are available with 4P and 3P + N CBs

                                                        Monitor time          Normal                Accuracy of
                                     Measurement
                                                        (min-max)             operating range       value read   (1)
                                     Line-to-line voltages  (6)  5 V ÷ 900 V  (9)  100 ÷ 690 V      0.5 %  (8)
                                     Phase voltages     5 V ÷ 900 V  (9)      50 ÷ 400 V            0.5 %  (8)
                                     Line frequency     30 ÷ 80 Hz   (2)      f -10 % ÷ f +10 %   (4)  0,1 %   (3)
                                     Total active, reactive and   |Pmin ÷ Pmax|  (5)  |0,3 ÷ 1,2 Sn|  2 %   (3)
                                     apparent power  (7)
                                     Active, reactive and           (5)                                 (3)
                                     apparent phase power  |Pmin ÷ Pmax|      |0,3 ÷ 1,2 Pn|        2 %

                                    (1)  the accuracies refer to normal operating ranges, as established by IEC 61557-12
                                    (2)  available for voltage values of over 30 V (with Un < 277 V) or 60 V (with Un > 277 V)
                                    (3)  accuracies based on Ekip Touch without Class 1 Power & Energy Metering package; if the Class 1 Power &
                                    Energy Metering package is present and for all other trip unit models, check the indicated performance values
                                    from page 117
                                    (4)  45 to 55 Hz with set frequency = 50 Hz; 54 to 66 Hz with f = 60 Hz
                                    (5)  Pmin = 0,5 In x 5 V; Pmax= 3 x 16 In x 900 V
                                    (6)  the higher line-to-line voltages are also available in the Histograms, Measuring instruments and Measurement
                                    summary pages
                                    (7)  the higher total powers are also available in the Measuring instruments and Measurement summary pages
                                    (8)  without transformers; 0.7 % with class 0.2 external transformers
                                    (9)  without transformers; with transformers, multiply the min and max values for the transformer ratio between
                                    primary and secondary voltages

                                                                                                  Continued on the next page








       114 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A            Ekip Touch - Measurements | 2 - Ekip Measuring Measurements