        Ekip Touch - Default




       1 - Ekip TOUCH default parameters



                          Foreword Given the number of parameters available with Ekip Touch, each chapter describing their characteristics also
                                    includes their default value settings.
                                    The configurations of the main parameters are given below.


                        Protections All Ekip Touch models are supplied with the protections (and relative correlated functions) off, with the
                                    exception of the protections listed below:
                                     Protection               Configuration
                                     L  (1)                   I1= 1 In;  t1= 144 s;  curve= t= k/I ;  prealarm: 90% I1
                                                                                       2
                                     I                        I3= 4 In;  startup= OFF
                                     Harmonic distortion      On
                                     Rc  (2)                  Idn= 3 A;  Tdn= 0,06 s

                                    (1)  protection always active; a model L Disable rating Plug must be used to disable it
                                    (2)  protection available and active if model Rc Rating Plus is present


                        Parameters Unless different specifications are requested when ordering, all Ekip Touch models are supplied with the
                                    following configurations:
                                     Parameters               Configuration
                                     Frequency                50 Hz (IEC) / 60 Hz (UL)
                                     Configuration            3P (3P circuit-breaker) / 4P (4P circuit-breaker)
                                     Neutral                  Off (3P circuit-breaker) / 50% (4P circuit-breaker)
                                     Rated voltage            400 V
                                     Power flow               Top → Bottom
                                     Phase Sequence           1-2-3
                                     Local bus                Off
                                     Mode                     Local
                                     Language                 English
                                     Bluetooth Low Energy     Off
                                     Password                 00001
                                     Home page                Histograms
                                     Led Alive                Disabled
                                     View                     Horizontal
                                     Maintenance              On
                                     Test Bus                 On
                                     Modbus RTU par           Address: 247; baudrate: 19.2 Kbit/s
                                     Profibus                 Address: 125
                                     DeviceNet  TM            MAC ID: 63; baudrate: 125 Kbit/s
                                     Modbus TCP/IP            Static IP: 0.0.0.0