Page 165 - Sace Emax 2 Manual for design engineers
P. 165

ABB | SACE Emax 2
       3 - Environmental conditions



             Installation environment Install the circuit-breaker in a dry environment, without dust or corrosive acids, and so that it is not subject
                                    to shock or vibration.
                                    If this is not possible, mount the circuit-breaker in a compartment protecting it adequately.
                                    For the dimensions to be considered for installation, see the chapter "4 - Installation" on page 165 where the
                                    references for following information can be found:
                                     •  minimum installation volumes of the circuit-breakers and derived versions in a cell
                                     •  overall dimensions of the circuit-breakers and the fixed parts
                                     •  drilling of mounting holes
                                     •  drilling of the cell door


       Temperatures of the installation  The mechanical and electrical characteristics are guaranteed between -25 ° C and +70 ° C, -13 °F e +158 °F.
                        environment

         Particular weather conditions The circuit breaker is designed to operate in particularly difficult industrial environments.
                                    It was tested according to:
                                     •  IEC 60068-2-1: endurance at low temperatures
                                     •  IEC 60068-2-2: hot dry climate
                                     •  IEC 60068-2-30: hot humid climate
                                     •  IEC 60068-2-52 severity 2: saline mist atmosphere
                                     •  IEC 60947 (pollution level ≤ 3)
                                     •  IEC60721-3-6 class 6C3
                                     •  IEC60721-3-3 class 3C2
                                           NOTE: the circuit-breaker is suitable for installation in environments with saline concentrations
                                               no higher than 10 mg/m3.



                 Dusty environments It is recommended to install the circuit breaker in suitably ventilated switchgear where penetration by dust is
                                    minimized.
                                    In case of dusty environments (dust> 1 mg/m3) second level maintenance procedures must be followed.


                           Vibration The circuit-breaker is insensitive to mechanical or electromagnetic vibrations that meet the following
                                    standards:
                                     •  IEC 60068-2-6  a) From 1 to 13 Hz with movement equal to 1 mm - 0.04 in  b) From 13 to 100 Hz with
                                       constant acceleration equal to 0.7 g - 0.025 lbs
                                     •  Shipping Registers' specifications: RINA, BV, GL, ABS, LRs, DNV



































       163 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                 Mechanical characteristics | 3 - Environmental conditions