                       Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply, either on the
                                    circuit-breaker (fixed version) or on the fixed part (withdrawable version).
                                    For references about the connection and terminals, please consult document  1SDM000091r0001; use
                                    AWG 22-16 cables with 1.4 mm maximum outer diameter for the external cabling.
                                    To connect the module to Ekip Touch, please consult document 1SDH001000r0513.


                       Power supply Ekip Com Synchrocheck is supplied directly by the Ekip Supply module to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence of
                                               auxiliary power supply



                              Input Ekip Synchrocheck has an input (V S1 - V S2) for reading voltage, operation of which is ensured within the
                                    ranges and with the performance given below:
                                     Component     Operating range     Normal operating range      Accuracy  (1)
                                     Voltage       0÷120 VAC           10 ÷ 120 VAC                1 %  (2)
                                     Frequency  (3)  30÷80 Hz          30 ÷ 80 Hz                  0,1 %  (4)
                                     Phase  (5)    -                   -180 ÷ +180 °               1 °

                                    (1)  the accuracy values refer to normal operating ranges, as established by IEC 61557-12
                                    (2)  with busbar activated
                                    (3)  with the busbar activated, frequency measurement starts at ≥ 36 V AC and ends at ≤ 32 V AC measured
                                    voltage
                                    (4)  in the absence of harmonic distortion
                                    (5)  phase measurement refers to the phase difference between internal and external voltage

                                    Isolation transformer
                                    An isolating transformer with the characteristics given below must always be installed between the external
                                    contacts of the circuit-breaker and the input of the module:
                                     Characteristics  Description
                                                     • fixing: EN 50022 DIN43880 rail
                                                     • material: self-extinguishing thermoplastic
                                     Mechanical
                                                     • protection class: IP30
                                                     • electrostatic protection: with earth connector shield
                                                     • accuracy class: ≤ 0,2
                                                     • performance: ≥ 4 VA
                                                     • overload: 20% permanent
                                     Electrical
                                                     • insulations: 4 kV between inputs and outputs, 4 kV between screen and outputs,
                                                    4 kV between screen and inputs
                                                     • frequency: 45 to 66 Hz




                            Output Ekip Synchrocheck has an output (K S1 - K S2) used as synchronism contact.
                                    The output is insulated from the unit and input, and has the following electrical characteristics:
                                     Characteristics                        Maximum limit  (1)
                                     Maximum switchable voltage             150 VDC / 250 VAC.
                                                                            2 A @ 30 VDC, 0,8 A @ 50 VDC, 0,2 A @ 150 VDC,
                                     Breaking capacity
                                                                            4A @ 250 VAC
                                     Dielectric strength between open contacts  1000 V AC (1 minute @ 50 Hz).
                                     Dielectric strength between each contact and coil  1000 V AC (1 minute @ 50 Hz).

                                    (1)  data relating to a resistive load