Page 224 - Sace Emax 2 Manual for design engineers
P. 224

ABB | SACE Emax 2
                              Menu The specific configuration area will activate in the Settings - Modules menu if the Ekip Signalling 2K module
                                    is detected correctly by Ekip Touch.
                                    A specific menu containing the submenus of all the available and configurable inputs and outputs is available
                                    for each Ekip Signalling 2K module detected by Ekip Touch.


                   Input parameters All the available inputs enable the following parameters to be configured:
                                     Parameter    Description                                              Default
                                                  Defines whether the input is interpreted as ON by Ekip Touch when it is open  Active
                                     Polarity
                                                  (Active open) or when it is closed (Active Closed)       closed
                                                  Minimum activation time of the input before status change is recognized; the
                                                  delay is given in seconds and can be set within range: 0 s to 100 s, in 0.01 s
                                                  steps
                                     Delay            NOTES:                                               0.1 s
                                                      • if the input is deactivated before this time has elapsed the status
                                                     change is not recognized
                                                      • if delay = 0 s status change must still be more than 300 µS




                  Output parameters All the available inputs enable the following parameters to be configured:
                                     Parameter    Description                                              Default
                                                  Event which activates the output and switches the contacts.
                                                  Different protection proposals, statuses and thresholds are available on the
                                     Signal source                                                         None
                                                  display; the Custom mode can be configured via Ekip Connect so as to
                                                  extend the solutions and combine several events
                                                  Minimum duration of the presence of the source before the output is
                                                  activated; the delay is given in seconds and can be set within range: 0 s to
                                                  100 s, in 0.01 s steps
                                     Delay            NOTES:                                               0 s
                                                       • the output will not be switched if the source is deactivated before this
                                                      time has elapsed
                                                       • if delay = 0 s the source must still be present for longer than 300 µS
                                                  Defines the rest status of the contact with source not present between: open
                                     Contact Type                                                          NO
                                                  (NO) and closed (NC)
                                                  Allows the output (and relative status led) to be kept activated (On) or
                                     Latched  (1)                                                          OFF
                                                  deactivated (Off) when the event disappears
                                                  Defines the minimum closing time of the contact following the rapid presence
                                                  of sources:
                                                   • Source duration < min. activation = contact is activated for the minimum
                                     min Activation
                                     Time  (2)    activation time                                          0 ms
                                                   • Source duration ≥ min. activation = contact is activated for as long as the
                                                  source persists
                                                  Choose between: 0 ms, 100 ms, 200 ms
                                    (1)  deactivate the latchings of the outputs used if the Measurement module is used for the Power Controller
                                    function
                                    (2)  if the Measurement module is used for the Power Controller function, the Power Controller option will also
                                    be available; if selected, the output is kept activated for a set time that depends on the function, regardless of
                                    whether the event that activated it persists


                             About The specific menu of the module available in the About - Modules menu contains:
                                     •  the serial number and version of the module
                                     •  the statuses of the inputs (On/Off) and outputs (Open/Closed)


                               Test The test area in the Test menu is activated if the Ekip Signalling 2K module is detected correctly.
                                    For details of the test characteristics, please consult page 134.


                 Remote information Certain additional information concerning the version and status of the module is available via the service
                                    connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
                                    version, CRC status (correctness of the SW in the module).


       222 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                 External electronic accessories | 11 - Ekip Signalling 2K