ABB | SACE Emax 2
                           Interface the module has three signaling leds:














                                    Figure 136
                                     LEDs           Description
                                                    Signals the on status and correct communication with Ekip Touch:
                                                     • off: module off
                                                     • on steady or flashing synchronized with the Power led of Ekip Touch: module on
                                     Power
                                                    and communication with Trip unit present, flashing not synchronized with the Power
                                                    led of Ekip Touch (two fast flashes per second): module on and communication with
                                                    Trip unit absent
                                                    Indicate the status of the contacts of each output:
                                                     • off: contact open
                                     O SC            • on: contact closed
                                                         NOTE: The LED shows the output status: it indicates synchronization OK or
                                                        KO, depending on the contact rest configuration (normally open or closed)




             Configurations via menu The specific configuration area will activate in the Advanced - Synchrocheck menu if the Ekip Synchrocheck
                                    module is detected correctly by Ekip Touch.
                                     Parameter      Description                                            Default
                                                    Activates/deactivates the protection and its availability in the parameters
                                     Enable                                                                Off
                                                    menu
                                     Dead bar option  On = busbar activated; Off = dead busbar present     Off
                                                    Maximum external voltage (with dead busbar and configuration: Normal
                                                                                                         (2)
                                     Udead T        is the first synchronism condition)                    0.2 Un
                                     hreshold  (1)(2)  The value is given as both absolute value (Volts) and relative value (Un)
                                                    and can be set within the range: 0.02 Un to 2 Un, in 0.001 Un steps
                                                    Minimum voltage for starting monitoring of external voltage (with busbar
                                     Ulive          activated) or internal voltage (with dead busbar and Normal configuration)  0.5 Un
                                     Threshold  (2)(3)  The value is given as both absolute value (Volts) and relative value (Un)
                                                    and can be set within the range: 0.5 Un to 1.1 Un, in 0.001 Un steps
                                                    Minimum time within which the Ulive Threshold condition must be
                                                    obtained in order to activate voltage monitoring
                                     Stability Time                                                        1 s
                                                    The value is given in seconds and can be set within the range: 100 ms to
                                                    30 s, in 1 ms steps
                                                    Maximum difference between internal and external voltage (first
                                                    synchronism condition)
                                     Delta Voltage                                                         0.12 Un
                                                    The value is given as both absolute value (Volts) and relative value (Un)
                                                    and can be set within the range: 0.02 Un to 0.12 Un, in 0.001 Un steps
                                                    Maximum difference between internal and external frequency (second
                                                    synchronism condition)
                                     Delta frequency  (4)                                                  0.1 Hz
                                                    The value is given in Hertz and can be set within the range: 0.1 Hz to 1
                                                    Hz in 0.1 Hz steps
                                                    Maximum difference between internal and external phase (third
                                                    synchronism condition)
                                     Delta phase  (4)                                                      50 °
                                                    The value is given in degrees and can be set within the range: 5° to 50° in
                                                    5° steps


                                                                                                  Continued on the next page