Page 231 - Sace Emax 2 Manual for design engineers
P. 231

ABB | SACE Emax 2
       13 - Ekip Signalling 3T



                                    Ekip Signalling 3T is a signaling accessory which enables the connection of:
                                     •  three analog inputs for PT100/PT1000 temperature sensors (2 wires): I42, I43, I44
                                     •  an analog input for 4-20mA current loop: I41
                                    The measurements supplied by the module can be associated with different control threshold, useful for
                                    configuring alarm signals, states and programmable commands.
                                           NOTE: PT100 temperature sensors are compatible only with Ekip Signalling 3T module
                                               installed on Emax 2 with black platform.


                            Models Ekip Touch can be configured with two different 3T modules: Ekip Signalling 3T-1 and Ekip Signalling 3T-2.

                                           NOTE: if different indications are not given, the information in the next chapter is valid for
                                               both models; on the second module the inputs are called I51 (lopp 4-20mA), I52, I53,
                                           I54 (PT100/PT1000)
                                    The  two  modules  can  be  installed  at  the  same  time  on  the  same  circuit-breaker  so  as  to  extend  the
                                    opportunities for measuring and monitoring the installation.
                                           IMPORTANT: each circuit-breaker can only be fitted with one module per type.
                                               Configuration with two modules of the same model is not allowed (example: two
                                           Ekip Signalling 3T-1 modules)



                       Connections For references about the connection and terminals, please consult document 1SDM000091r0001
                                    To connect the module to Ekip Touch, please consult document 1SDH001000r0527.
                                    For PT100/PT1000 sensors, use insulated cables for resistance thermometers such as PENTRONIC TEC/
                                    SITW-24F (Type TX) or similar. Maximum length 3 meters.
                                    For the 4-20mA Current Loop sensor, use suitable cables up to 3 meters in length compatible with the
                                    workplace in which the 4-20mA current sensor is used.
                                           IMPORTANT: the inputs are not insulated: regardless of plant voltage, the customer
                                               must ensure there is insulation between each input and between the inputs and
                                           power supply of the Ekip Supply module on the basis of the customer's own application
                                           and network.

                                           For applications in low voltage installations ABB suggests use of the external probe
                                           PT1000 3mt, is equippped with a nut and screw for use on busbars and is compatible
                                           with the dielectric withstand and insulation levels established by standard IEC 60947-
                                           2 (Ui= 1000 V, Uimp= 12 kV).


                       Power supply Ekip Signalling 3T is supplied directly by the Ekip Supply module to which it is connected.

                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence of
                                               auxiliary power supply























       229 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                  External electronic accessories | 13 - Ekip Signalling 3T
   226   227   228   229   230   231   232   233   234   235   236