Page 46 - Sace Emax 2 Manual for design engineers
P. 46
ABB | SACE Emax 2
Advanced menus The Advanced menu can be used to configure the following protections :
(1)
Name Parameters SW package Page
MCR List in dedicated chapter 58
2I List in dedicated chapter Standard 59
Protections
IU List in dedicated chapter 60
UV (2) List in dedicated chapter 62
OV (2) List in dedicated chapter 63
UV2 (2) List in dedicated chapter Voltage protections 63
OV2 (2) List in dedicated chapter 64
VU (2) List in dedicated chapter 64
S(V) (2) List in dedicated chapter 65
S2(V) (2) List in dedicated chapter Voltage Advanced 66
protections
RV (2) List in dedicated chapter 68
UF (2) List in dedicated chapter 69
OF (2) List in dedicated chapter Frequency 70
UF2 (2) List in dedicated chapter protections 70
OF2 (2) List in dedicated chapter 71
RP (2) List in dedicated chapter 72
D (2) List in dedicated chapter 73
RQ (2) List in dedicated chapter Power protections 76
OQ (2) List in dedicated chapter 75
UP (2) List in dedicated chapter 76
OP (2) List in dedicated chapter 75
ROCOF (2) List in dedicated chapter ROCOF protections 78
V DIR, VINV (2) List in dedicated chapter 142
59 S1 (2) List in dedicated chapter Interface 142
protections (IPS)
Warnings VS Warning, FS Warning, FW1 Warning 142
Threshold 1 I1, Threshold 2 I1, Threshold Iw1,
Signallings Standard 92
(2)
Threshold Iw2, Phase Sequence , CosØ (3)
Protections
Functions External Trip, Trip Reset, Switch On SET B (4) 92
Synchrocheck List in dedicated chapter (5) 89
RC List in dedicated chapter (6) 87
(1) if the Adaptive Protections package is available and Dual set has been activated, an intermediate menu
where the set can be selected (Set A / Set B) will be available before the list of protections The only menu
always present via Advanced is Functions
(2) available if provided for by Trip unit model or if the relative SW package has been activated, where possible
(page 14)
(3) CosØ available if provided for by Trip unit model or if the Power Protections package has been activated
(4) SET B available when Adaptive Protections package is present
(5) available when Ekip Synchrocheck is present
(6) available when Rating Plug type Rc is installed in unit and when presence of toroid Rc has been
previously activated in Settings menu
44 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Ekip Touch - Interface and menus | 4 - Menu