        Ekip Touch - Protections




       1 - Protections - Introduction



                  Operating principle The protection functions are available with all Ekip Touch models and versions.
                                    Each protection is associated with a different signal (current, voltages, frequencies, powers, etc) but the
                                    operating principle is the same:
                                      1.  If the signal measured exceeds the set threshold, the specific protection activates (prealarm and/or
                                         alarm).
                                      2.  The alarm appears on the display and, after a period of time (timing t ), depending on the protection
                                                                                             t
                                         parameters set, can convert into a trip command (TRIP) transmitted to the internal Trip coil of the
                                         CB.
                                           NOTE:
                                            •  if the signal measured drops below the set threshold before the trip time has elapsed, Ekip
                                              Touch quits the alarm and/or timing status and returns to the normal operating condition
                                            •  all protections have a default configuration: check the parameters and change to suit the
                                              installation requirements before putting into service


                         References Many of the protection thresholds are displayed in two different quantities: absolute value and relative value.
                                    The relative value depends on the type of measurement:
                                     Type of protection  Reference          Description
                                     Current            In                  Nominal current of the Rating plug
                                     Voltage            Un                  Line-to-line voltage setting
                                     Frequency          fn                  Frequency setting
                                     Power              Sn                  √3 x In x Un



               Protections packages The protections described in the following chapters are grouped into packages, the availability of which
                                    depends on the model and version of the Trip unit, and on their ability to be installed as additional package:
                                     Package                                             Page
                                     Standard Protections                                52
                                     Voltage protections                                 62
                                     Voltage Advanced protections                        65
                                     Frequency protections                               69
                                     Power protections                                   72
                                     Adaptive protections                                79





























       51 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                   Ekip Touch - Protections | 1 - Protections - Introduction