Page 57 - Sace Emax 2 Manual for design engineers
P. 57

ABB | SACE Emax 2
                       S2 Protection Function
                                    S2 protection functions in the same way as S protection: if the current of one or more phases exceeds
                  t                 threshold I5 for longer than time t5, the protection activates and sends a TRIP command.
                       I5     S2
                                           NOTE: unlike S protection, S2 protection only has one fixed time trip curve and has no thermal
                                               memory
                            t5
                                    It is independent of S protection, thus thresholds and functions of the two protections can be programmed
                                    so as to take advantage of different plant solutions (example: signaling with S and open command with S2 or
                                  I  vice versa, or both S and S2 for signaling or tripping).
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  the summary table of the protections with the calculation formulas (page 92)
                                     •  the graph with trip curve (page 98)
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu.
                                                  Activates/deactivates transmission of the open command. if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   ON
                                                  information.
                                                  Establishes the value that activates the protection and contributes
                                                  towards calculating the trip time.
                                     Threshold I5                                                     4 In
                                                  The value is given as both absolute value (A) and relative value (In) and
                                                  can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                  This is the trip time of the protection.
                                     Time t5      The value is given in seconds and can be set within the range: 0.05 s  0,05 s
                                                  to 0.8 s, in 0.01 s steps
                                                  Activates/deactivates the function and selectivity time availability on
                                                  the display (page 80)
                                                      NOTE: if both S and S2 selectivities are activated, the input and
                                     ZoneSelectivity                                                  OFF
                                                     output are shared with the OR function; to stimulate inputs and
                                                     outputs, it is sufficient for even only one of the two to be
                                                     activated
                                                  This is the trip time of the protection with the zone selectivity function
                                                  activated and selectivity input not present (page 80)
                                     Selectivity time                                                 0,04 s
                                                  The value is given in seconds and can be set within the range: 0.04 s
                                                  to 0.2 s, in 0.01 s steps
                                                  Activates/deactivates the function and availability of the associated
                                     StartUp enable                                                   OFF
                                                  parameters on the display (page 83)
                                                  Protection threshold valid during Startup time, in the conditions in
                                     StartUp      which the function is activated (page 83)           4 In
                                     Threshold    The value is given as both absolute value (A) and relative value (In) and
                                                  can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                  This is the time for which the StartUp threshold remains activated and
                                                  is calculated from the moment the activation Threshold is exceeded
                                     StartUp Time  (page 83)                                          0.1 s
                                                  The value is given in seconds and can be set within the range: 0.1 s to
                                                  30 s, in 0.01 s steps

                                    Limitations and additional functions
                                     •  threshold I5 must be higher than threshold I1 (if S2 protection is activated)
                                     •  the block functions and type of selectivity can also be accessed by means of the service connector (via
                                       Ekip Connect) or communication via system bus (page 82)
                                     •  with CB in UL standard configuration, the maximum value of t5 is 400 ms


















       55 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                     Ekip Touch - Protections | 2 - Standard Protections