Page 58 - Sace Emax 2 Manual for design engineers
P. 58

ABB | SACE Emax 2
                        I Protection Function
                                    If the current of one or more phases exceeds threshold I3, the protection trips and, after a non-programmable
                  t                 fixed time, transmits the TRIP command.
                       I3      I    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 92)
                                     •  the graph with trip curve (page 99)
                                    Parameters
                                  I  Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           ON
                                                  parameters menu.
                                                  Establishes the value that activates the protection.
                                     Threshold I3  The value is given as both absolute value (A) and relative value (In) and  4 In
                                                  can be set within the range: 1.5 In to 15 In, in 0.1 In steps
                                     ZoneSelectivity  Activates/deactivates the function              OFF
                                                  Activates/deactivates the function and availability of the associated
                                     StartUp enable                                                   OFF
                                                  parameters on the display (page 82)
                                                  Protection threshold valid during Startup time, in the conditions in
                                     StartUp      which the function is activated (page 82)           1,5 In
                                     Threshold    The value is given as both absolute value (A) and relative value (In) and
                                                  can be set within the range: 1.5 In to 15 In, in 0.1 In steps
                                                  This is the time for which the StartUp threshold remains activated and
                                                  is calculated from the moment the activation Threshold is exceeded
                                     StartUp Time  (page 82)                                          0.1 s
                                                  The value is given in seconds and can be set within the range: 0.1 s to
                                                  30 s, in 0.01 s steps

                                    Limitations and additional functions
                                     •  threshold I3 must be higher than threshold I2 (if S and I protections are activated)
                                     •  I protection can be activated with MCR protection disabled
                                     •  the  block functions  can also be accessed by means  of the service  connector (via Ekip Connect) or
                                       communication via system bus (page 83)
















































       56 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                     Ekip Touch - Protections | 2 - Standard Protections