Page 141 - SACE Tmax XT - Catalogue
P. 141

SOLUTIONS                                                                         6/7



          —

          Adaptive Protections




          The Tmax XT adds a dual setting capability to the
          switching device to ensure continuous coordination





                           Purpose                                     Application example
                           User’s plants can work as an LV Microgrid thanks   A plant is connected to the MV utility by means of
                           to the energy produced by renewable and local   an MV/LV transformer. If the utility shuts down,
                           power sources, in particular as a consequence of   the plant will become a microgrid supplied by a
                           the lack of a utility power supply, e.g. due to a   local generator G, which will feed priority loads by
                           fault on the MV voltage side. In order to still guar-  using the load shedding feature of the Tmax XT.
                           antee a high level of selectivity and continuity of   In a grid-connected condition, the generator G is
                           service, it is important to take into account the   disconnected. With reference to Fig. 1:
                           variation of the short-circuit power when moving   •  Circuit-breaker A is closed
                           from on-grid to off-grid operation.         •  Circuit-breaker B is open
                           Indeed, during grid connected conditions the   •  Circuit-breakers at position C are closed. The
                           fault current on a microgrid feeder is also sup-  protection of the circuit-breaker at C that sup-
                           plied by the utility, thus resulting higher than the   plies the feeders at D are adjusted using "Set A"
                           one supplied only by local generation during is-  of the Tmax XT unit.
                           landed conditions. As a result, it is desirable that   •  Circuit-breakers at position D are closed
                           several protection thresholds of the units can be   •  Circuit-breaker E is closed
                           automatically changed during the transition to is-  •  Switch-disconnector QS1 is closed
                           landing conditions.                         •  All loads are supplied.
                                                                       The circuit-breakers at position C are selectively   06
                                                                       coordinated with the upstream main cir-
                                                                       cuit-breaker A, supplied by the utility, and the
                                                                       downstream load circuit-breakers at position D
                                                                       (see Fig. 2 at the following page).
                                                   U





                                                                                 G


                                              A                             B







                               E                                   C               C               C






                              non priority loads
                                                                          QS1


                                                       D           D            D



                           —
                           Fig. 1
   136   137   138   139   140   141   142   143   144   145   146