Page 142 - SACE Tmax XT - Catalogue
P. 142

6/8              SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Adaptive Protections













                           With the adaptive protections, when there is an   Benefits
                           utility outage, circuit-breaker A opens and B closes   Thanks to the Tmax XT it is possible to have two
                           in order to achieve an islanded condition. In order   sets of settings implemented in a single device.
                           to still guarantee selectivity, another set of  As a result, the following benefits are guaranteed:
                           protection settings is required. Adding Tmax XT   •  Overcurrent protection and selectivity 100%
                           adaptive protections to the circuit-breaker C1 en-  guaranteed both in grid-connected and is-
                           sure this behaviour. The second protection set-  landed conditions.
                           ting is optimized for the characteristics of the lo-  •  Service continuity is garanted by just adding a
                           cal generator ensuring the incoming supply.   single unit to the switchboard in every plant
                           Additionally, selective coordination with the load   condition.
                           side switching devices is also guaranteed.  •  Ease of use, thanks to the Ekip Connect soft-
                           With reference to Fig. 1:                    ware which allows an immediate and intuitive
                           •  Circuit-breaker A is open                 commissioning phase.
                           •  Circuit-breaker B is closed
                           •  Circuit-breakers at position C are closed and the
                            protection thresholds move automatically to
                            “Set B”
                           •  Circuit-breakers at position D are closed
                           •  Circuit-breaker E is open
                           •  Switch-disconnector QS1 is closed
                           •  Non-priority loads can be disconnected using
                            another functionality of the Tmax XT units (see
                            next paragraph).

                           Fig. 3 shows how it is possible to switch to a set
                           of parameters which guarantees selective coordi-
                           nation between circuit-breakers C and B by
                           means of the Adaptive Protection function em-
                           bedded in the trip unit of the C circuit-breakers.







                            10 3 s                                     10 3 s
                                               A                                       B
                            10 2 s                                      10 2 s
                            10s                                         10s
                                                C                                           C
                                           D                                          D
                             1s                                         1s
                           10 -1 s                                     10 -1 s
                           10 -2 s                                     10 -2 s
                           10 -3 s                                     10 -3 s                    10 2 kA   10 3 kA
                                    1kA      10kA     10 2 kA   10 3 kA         1kA      10kA
                           Time-Current curves                         Time-Current curves
                           —                                           —
                           Fig. 2 - Protection thresholds during on-grid operation  Fig. 3 - Protection thresholds during islanded operation
   137   138   139   140   141   142   143   144   145   146   147