7/62             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Residual current protection














         Power supply Voltage                              /A    AC [V]     115-230...415
                                                           /P    AC [V]     110...690
                                                           /P    DC [V]     110...125
         Operating frequency                                     [Hz]       45÷66
         Inrush current                                    /A    @115 V AC  500 mA for 50 ms
                                                           /A    @230 V AC  150 mA for 50 ms
                                                           /A    @415 V AC  100 mA for 50 ms
                                                           /P    @110 V AC  300 mA for 50 ms
                                                           /P    @690 V AC  2 A for 50 ms
                                                           /P    @125 V DC  500 mA for 50 ms
         Rated Power                                       /A               2 [VA] / 2 [W]
                                                           /P    @115 V AC  max 3 W
                                                           /P    @230 V AC  max 3 W
                                                           /P    @690 V AC  max 4 W
                                                           /P    @125 V DC  max 2 W
         Trip threshold adjustment IΔn                           [A]        0.03-0.05-0.1-0.3-0.5-1-3-5-10-30
         No trip time adjustment                                 [s]        instantaneous 0.1-0.2-0.3-0.5-0.7-1-2-3-5
         Pre-alarm threshold                                     x IΔn      25%
         A type for pulsing alternate current                               
         Signals
         Device powered visual signaling                                    
         Visual signaling of device not functioning / not configured        
         Visual signaling of residual current protection                    
         Electrical alarm/pre-alarm signal                                  
         Electric trip signal                                               
         Controls
         Remotely controlled opening command                                
         Remotely controlled reset command                                  
         Operating range of closed transformers
         Ø 60 [mm] toroidal transformer                          [A]        In max = 250 A - Use 0.03...30 A
         Ø 110 [mm] toroidal transformer                         [A]        In max = 400 A - Use 0.03...30 A
         Ø 185 [mm] toroidal transformer                         [A]        In max = 800 A - Use 0.1...30 A
         Connection to toroidal transformer                                 By means of 4 shielded or twisted conductors.
                                                                            Maximum tolerated length: 15 m
         Dimensions W x H x D                                    [mm]       96 x 96 x 77
         Drilling for assembly on door                           [mm]       92 x 92
         standard                                                           IEC 60947-2 annex M