Page 205 - SACE Tmax XT - Catalogue
P. 205
ACCESSORIES 7/59
Electrical characteristics Residual current devices
RC B Type XT3
Primary power supply voltage [V] 110…500
Operating frequency [Hz] 45…66
Fault frequency [Hz] 400-700-1000
Test operating range [V] 110…500
Rated operating current [A] up to 225
Adjustable trip thresholds [A] 0.03-0.05-0.1-0.3-0.5-1
Selective type S
Adjustable NON-trip time settings [s] at 2xIΔn Instantaneous 0-0.1-0.2-0.3-0.5-1-2-3
Power input <10 W at 500V AC
Trip Coil with switch contact for trip signal
Input for remote controlled opening command
NO contact for pre-alarm signal
NO contact for alarm signal
Steady yellow LED light
Flashing yellow LED light (1)
Type A for pulsating alternating current, Type AC for alternating current
Type B for pulsating current and direct current
(1) Indication of alarm timing at 90% I∆n for 30mA
07