7/60             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Residual current protection













                           SACE RCQ020 panel type residual current release
                           SACE Tmax XT circuit-breakers can also be used in conjunction with RCQ020 panel type residual current
                           releases with a separate toroid to be installed on the line conductors (“/A” indicates the necessity for an
                           auxiliary power supply).
                           Thanks to its wide range of settings, the panel release is suitable for:
                           •  applications where the installation conditions are particularly restrictive, such as for circuit-breakers
                            that are already installed or where there is limited space in a compartment where the circuit-breaker
                            is installed;
                           •  creating a residual current protection system coordinated at various distribution levels, from the
                            main switchboard to the end user;
                           •  where residual current protection with low sensitivity is required, e.g. in partial (current) or total
                            (time) selective chains;
                           •  highly sensitive applications (physiological sensitivity) for protecting people against direct contacts.
                           Thanks to the 115-230...415V external auxiliary power supply, the RCQ020 panel type residual current
                           device is able to detect current leakages from 30mA to 30A and to act with a trip time that can be ad-
                           justed from instantaneous to a delay of 5s. The opening mechanism is an indirect action type and acts
                           on the circuit-breaker release mechanism by means of the shunt opening or an undervoltage release of
                           the circuit-breaker itself.
                           The opening command to the circuit-breaker (trip delay) can be temporarily inhibited, and the circuit-
                           breaker can be opened by remote control by means of the RCQ020 device.
                           The following equipment must be requested when ordering:
                           •  the RCQ020 device itself;
                           •  an opening coil (SOR) or an undervoltage release (UVR) of the circuit-breaker to be housed in the rela-
                            tive slot made in the left pole of the circuit-breaker itself;
                           •  a closed toroid, which can be used for both cables and busbars, with a diameter from 60mm to 185mm.

                           Signals available:
                           •  LED to indicate the status of the residual current device (supplied or not supplied). The RCQ020 is
                            equipped with a positive safety function thanks to which the RCQ020 sends an automatic circuit-
                            breaker opening command in the absence of auxiliary voltage;
                           •  LED for fault signaling;
                           •  LED for signaling tripping of the residual current device;
                           •  electrical pre-alarm/alarm/trip signals.