3/16 SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS
—
Offer
The Tmax XT trip units represent the ideal solution for any application up to 1600A.
The Tmax XT molded case circuit-breaker family The power distribution and generator protection
complies with numerous installation requirements. application trip units are available in both 3 and
Circuit-breakers are available with trip units 4-pole versions. With the XT2, XT4, XT5, XT6, XT7
dedicated to three different application groups. and XT7 M versions the trip units are inter-
The table below shows the trip units for each changeable, in order to make a performance up-
circuit-breaker frame and the related rated grade of the system easier.
interrupted current ranges.
Rated uninterrupted
current ranges [A] XT1 XT2 XT3 XT4 XT5 XT6 XT7 XT7 M
Power Distribution Protection
Thermal-magnetic
TMD 16…160 (1) 1,6…32 63…250 16…32
TMA 40…160 40…250 320…630 630...800
Ekip Dip
Ekip Dip LS/I 10…160 40…250 250…630 630…1000 630…1600 630…1600
Ekip Dip LIG 10…160 40…250 250…630 630…1000 630…1600 630…1600
Ekip Dip LSI 10…160 40…250 250…630 630…1000 630…1600 630…1600
Ekip Dip LSIG 10…160 40…250 250…630 630…1000 630…1600 630…1600
Ekip Touch
Ekip Touch LSI 40…160 100…250 250…630 630…1600 630…1600
Ekip Touch LSIG 40…160 100…250 250…630 630…1600 630…1600
Ekip Touch Measuring LSI 40…160 100…250 250…630 630…1600 630…1600
Ekip Touch Measuring LSIG 40…160 100…250 250…630 630…1600 630…1600
Ekip Hi-Touch LSI 40…160 100…250 250…630 630…1600 630…1600
Ekip Hi-Touch LSIG 40…160 100…250 250…630 630…1600 630…1600
Motor Protection
Magnetic
MF/MA 1…160 100…200 10…200 320…500
Ekip Dip
Ekip M Dip I 10…160 40…250 250…630 630…1000 630…1600 630…1600
Ekip M Dip LIU 25…160 40…160 250…500 630...800
Ekip Touch
Ekip M Touch LRIU 40…100 100…200 250…500 630…1600 630…1600
Generator Protection
Thermal-magnetic
TMG 16…160 63…250 320…630
Ekip Dip
Ekip G Dip LS/I 25…160 40…250 250…630 630…1000 630…1600 630…1600
Ekip Touch
Ekip G Touch LSIG 250…630 630…1600 630…1600
Ekip G Hi-Touch LSIG 250…630 630…1600 630…1600
1) 16A and 20A for N, S, H have the TMF trip unit