Page 55 - SACE Tmax XT - Catalogue
P. 55
PROTECTION TRIP UNITS 3/21
03
Available settings for MA and TMG trip units:
Circuit Trip In [A] L - Overload I - Short-circuit
Breaker Unit I1 [A] Neutral [A] I3 [A] Neutral [A]
MIN MED MAX 100% 50% MIN MED MAX 100% 50%
XT2 MF 1 14
2 28
4 56
8.5 120
12.5 175
MA 20 120 200 280
32 192 320 448
52 314 520 728
80 480 800 1120
100 600 1000 1400
160 960 1600 2240
XT3 MA 100 600 900 1200
125 750 1125 1500
160 960 1440 1920
200 1200 1800 2400
XT4 MA 10 50 75 100
12.5 62.5 93.7 125
20 100 150 200
32 160 240 320
52 260 390 520
80 400 600 800
100 500 750 1000
125 625 937.5 1250
160 800 1200 1600
200 1000 1500 2000
XT5 MA 320 2240 3200 4160
400 2800 4000 5200
500 3500 5000 6500
XT2 TMG 16 11 14 16 16 160 160
20 14 17 20 20 160 160
25 18 21 25 25 160 160
32 22 27 32 32 160 160
40 28 34 40 40 200 200
50 35 43 50 50 200 200
63 44 54 63 63 200 200
80 56 68 80 80 240 240
100 70 85 100 100 300 300
125 88 106 125 125 375 375
160 112 136 160 160 480 480
XT3 TMG 63 44 54 63 63 400 400
80 56 68 80 80 400 400
100 70 85 100 100 400 400
125 88 106 125 125 400 400
160 112 136 160 160 480 480
200 140 170 200 200 600 600
250 175 213 250 250 750 750
XT5 TMG 320 224 272 320 320 800 1200 1600 1600
400 280 340 400 400 1000 1500 2000 2000
500 350 425 500 500 1250 1875 2500 2500
630 441 536 630 630 1575 2363 3150 3150