Page 53 - SACE Tmax XT - Catalogue
P. 53

PROTECTION TRIP UNITS                                                            3/19



















                                                                                                                       03

                           Field of application  Trip Unit  L - Overload Protection  I - Short-circuit Protection
                                                       Current Threshold  Trip Time  Current Threshold  Trip Time
                           Power Distribution    TMD   Adjustable    Fixed         Fixed         Fixed instantaneous
                           Protection
                                              TMA      Adjustable    Fixed         Adjustable    Fixed instantaneous
                           Motor Protection   MA       -             -             Adjustable    Fixed instantaneous
                           Generator Protection  TMG   Adjustable    Fixed         Adjustable    Fixed instantaneous

                           Power Distribution Protection
                           TMD
                           In [A] 1.6  2  2.5  3.2  4  5  6.3  8  10  12.5 16  20  25  32  40  50  63  80  125 160 200 250
                           XT1                                      ●  ●   ●   ●  ●   ●   ●  ●   ●   ●
                           XT2  ●  ●   ●  ●   ●  ●   ●  ●   ●   ●   ●  ●   ●   ●
                           XT3                                                            ●  ●   ●   ●  ●   ●
                           XT4                                      ●  ●   ●   ●
                           Note: the XT1 with In = 16A or 20A and with N, S and H breaking capacity have the TMF trip unit only

                           TMA
                           In [A]  40  50  63   80   100   125  160  200  225   250  320  400   500  630  800
                           XT2  ●     ●    ●    ●    ●     ●    ●
                           XT4  ●     ●    ●    ●    ●     ●    ●    ●    ●     ●
                           XT5                                                       ●    ●     ●    ●
                           XT6                                                                       ●    ●

                           Motor Protection
                           MA
                           In [A] 1  2  3.2  4  6.3  8.5  10  12.5 16  20  32  52  63  80  100 125 160 200 320 400 500 630
                           XT2  ●  ●      ●      ●      ●       ●   ●  ●       ●  ●       ●
                           XT3                                                    ●   ●   ●  ●
                           XT4                       ●  ●       ●   ●  ●       ●  ●   ●   ●  ●
                           XT5                                                                   ●   ●  ●   ●
                           Note: the XT2 and XT4 up to 12.5A are available only as complete circuit-breakers
                                       the XT4 V and X versions up to 52A are available only as complete circuit-breakers with the Icu value at 690V AC = 5kA
                                       the XT2 up to 12.5A have the MF trip unit with fixed short-circuit protection
                           Generator Protection
                           TMG
                           In [A] 16  20  25  32   40  50   63   80  100  125  160  200  250  320  400  500  630
                           XT2  ●   ●    ●    ●    ●   ●    ●    ●   ●    ●    ●
                           XT3                              ●    ●   ●    ●    ●   ●    ●
                           XT5                                                               ●    ●   ●    ●
                           Note:  the XT2 up to 63A are available only as complete circuit-breakers
   48   49   50   51   52   53   54   55   56   57   58