3/24             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Ekip Dip


          Protection settings









          Available settings for Ekip Dip trip units:


          Ekip DIP LS/I& Ekip DIP LIG
          ABB code  Protection Function  Threshold               Trip Time                      Trip Curve
          L      Overload         I1 = 0.4...1 x In with steps of 0.04  t1 at 3 x I1 = 12 - 36s  t=k/I  2
                                                                 12 - 48s for XT7
          S      Selective short-circuit I2 = Off – 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4.5 - 5.5 –  t2 = 0.1 - 0.2s   t=k
                                  6.5 – 7 – 7.5 – 8 – 8.5 – 9 – 10 x In  at 10 x In when t = k/I  2  t = k or t = k/I   for XT7
                                                                                                         2
          I      Short-circuit    I3 = Off – 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4.5 - 5.5 –  t3 ≤ 20ms  t=k
                                  6.5 – 7 – 7.5 – 8 – 8.5 – 9 – 10 x In  t3 ≤ 30ms for XT7
          G      Earth fault      I4 = Off - 0.20 - 0 .25 - 0.45 - 0.55 - 0.75 - 0.80  t4 = 0.1 - 0.2 - 0.4 - 0.8s  t=k
                                  – 1 x In                       at 3 x In when t = k/I 2       t = k or t = k/I   for XT7
                                                                                                         2
                                  I4 = Off - 0.2 - 0.3 - 0.4 - 0.6 - 0.8 - 0.9 - 1.0 x In
                                  for XT7
          Ekip DIP LSI & Ekip DIP LSIG
          ABB code  Protection Function  Threshold               Trip Time                      Trip Curve
          L      Overload         I1 = 0.4...1 x In with steps of 0.02  t1 at 3xI1 =            t=k/I  2
                                  I1 = 0.4 - 0.42 - 0.45 - 0.47 - 0.5 - 0.52 - 0.55 -   3 - 12 - 36 - 60s at 3xI1 for XT2-XT4
                                  0.57 - 0.6 - 0.62 - 0.65 - 0.67 - 0.7  3 - 12 - 36 - 48s for XT5
                                  - 0.72 - 0.75 - 0.77 - 0.8 - 0.82 - 0.85 - 0.87 - 0.9  3 - 12 - 36 - MAX for XT6
                                  - 0.92 - 0.95 - 0.97 - 1 x In for XT7  3 - 12 - 24 - 36 - 48 - 72 - 108 - 144s for XT7
          S      Selective short-circuit I2 = Off – 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4.5 - 5.5 –  t2 = 0.05 - 0.1 - 0.2 - 0.4 for XT2-XT4-XT5-XT6 t = k or t = k/I  2
                                  6.5 – 7 – 7.5 – 8 – 8.5 – 9 – 10 x In  t2 = 0.1 - 0.2 - 0.3 – 0.4 – 0.5 – 0.6 – 0.7 – 0.8
                                  I2 = Off – 0.6 - 0.8  - 1 – 1.5 – 2 – 2.5 – 3 – 3.5 –  for XT7
                                  4 - 5 - 6 – 7 – 8  – 9 – 10 for XT7  at 10xIn when t = k/I  2
          I      Short-circuit    I3 = Off – 1 – 1.5 – 2 – 2.5 – 3 – 3.5 – 4.5 - 5.5 –  t3 ≤ 40ms  t=k
                                  6.5 – 7 – 7.5 – 8 – 8.5 – 9 – 10 x In  t3 ≤ 30ms for XT7
                                  I3 = Off – 1 .5 – 2 – 3 – 4 - 5 - 6 - 7 - 8 - 9 - 10 -
                                  11 - 12 -13 - 14 - 15 for XT7
          G      Earth fault      I4 = Off - 0.20 - 0 .25 - 0.45 - 0.55 - 0.75 - 0.80  t4 = 0.1 - 0.2 - 0.4 - 0.8s  t=k
                                                                                                         2
                                  – 1 x In                       at 3 x In when t = k/I 2       t = k or t = k/I  for XT7
                                  I4 = Off - 0.1 - 0.2 - 0.3 - 0.4 - 0.6 - 0.8 - 0.9 -
                                  1.0 x In for XT7
          Note: t1 MAX for XT6: 42s for XT6 1000 and 72s for XT6 800