Page 56 - SACE Tmax XT - Catalogue
P. 56

3/22             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Ekip Dip


          Overview








                           —                                           Power Distribution Protection

                           The Ekip Dip is a first level of            •  Ekip Dip LS/I
                                                                       •  Ekip Dip LIG
                           electronic trip unit, used for the          •  Ekip Dip LSI
                           protection of AC networks.                  •  Ekip Dip LSIG
                                                                       Motor Protection
                                                                       •  Ekip M Dip I
                                                                       •  Ekip M Dip LIU
                                                                       Generator Protection
                                                                       •  Ekip G Dip LS/I



          —                                                                                             3
          Key:                   1
          1.Dip switches for
           an overload                                                                                  4
           protection setting.
          2. Dip switches for
           short-circuit and time   2                                                                   5
           delayed short-circuit
           protection settings.
          3. Slot for lead seal.
          4. Test connector.
          5. Power-on LED.
                           Dip switches                                Thermal memory
                           The dip switches on the front of the trip unit allow   All the Ekip Dip trip units include a thermal mem-
                           manual settings also when the trip unit is off.  ory function. The trip unit records the trips which
                                                                       have occurred in the last few minutes. Since the
                           LEDs                                        trip causes overheating, in order to protect the
                           The LEDs on the front indicate the status of the   cables and let them cool down, the trip unit im-
                           release (on/off) and provide information about   poses a shorter delay tripping time in case of a
                           the protection tripped when the Ekip TT acces-  fault. This way, the system is protected against
                           sory is connected.                          damage due to cumulative overheating. This can
                                                                       be disabled, if needed, by using the Ekip T&P.
                           Front connector
                           The connector on the front of the unit allows the   External neutral
                           connection of:                              Ekip Dip trip units are available in both 3 and 4
                           • Ekip TT for trip testing; LED-test and signaling      poles. The 3-pole version with earth fault protec-
                             of the most recent trip.                  tion (G) can be equipped with an external sensor
                           • Ekip T&P, for connection to a laptop with the   for the neutral phase. In this way, the external
                            Ekip Connect program (thus measurement     neutral phase is protected and uninterrupted.
                            reading, as well as trip and protection function
                            tests are made available for the user).    Communication
                                                                       •  Using the dedicated Ekip Com module, XT2 and
                                                                        XT4 can communicate with Modbus RTU when
                           Characteristics of electronic Ekip Dip trip units
                                                                        they are equipped with the following trip units:
                           Operating temperature    -25°C…+70°C        •  Ekip LSI
                           Relative humidity        98%                •  Ekip LSIG.
                           Self-supplied            0.2xIn (single phase)*
                           Auxiliary supply (where applicable) 24V DC ± 20%
                           Operating Frequency      45…66Hz
                           Electromagnetic compatibility  IEC 60947-2 Annex F
                           *For 10A: 0.4xIn