SPDs for Building Systems


        BUStector
                                                             • Surge arrester for KNX / EIB buses
                                                             • Extremely space-saving due to KNX / EIB
                                                               bus terminal design
                                                             • System-tested with EIBA certification












        Surge arrester for KNX / EIB buses with connection wires.

        The  discharge  capacity,  protective  effect  and  mechanical  design  of   cables. BUStector surge arresters can also be connected to an existing bus
        BUStector surge arresters are adapted to the installation environment of   terminal on the terminal device. They particularly protect line and area
        KNX / EIB buses. Like bus terminals, they can be plugged onto the bus   couplers as well as gateways and sensors installed on the outer walls of
        terminal pins of a terminal device connected using the existing connecting   buildings.
























        Protection of a KNX power supply unit by means of a BUStector surge arrester   Protection of a KNX bus coupling unit by means of a BUStector surge arrester
        mounted in the standard bus terminal slot.           mounted on a bus terminal in the mounting panel of a cable duct.





   SPDs for   Building Systems  925 001   BT 24  BT
                         Surge arrester with KNX bus terminal design, adapted to the immunity of KNX / EIB systems. EIBA-certified.
          925 001     4013364047365  04 02 07 02   10 g
         79,00 €
                          Type                                BT 24
                          Part No.                            925 001
                          SPD class                           B
                          Max. continuous operating voltage (d.c.)  (UC)  45 V
                          Nominal current  (IL)               6 A
                          D1 Lightning impulse current (10/350 µs) per line  1 kA
                          C2 Nominal discharge current per line  (In)  5 kA
                          Cut-off frequency line-line  (fG)   70 MHz
                          Approvals                           EIBA certification No. Z 32/1399/95, EAC