                         DBX TC B 180
        922 220   DBX TC B 180
                         Compact surge arrester in a surface-mounted plastic enclosure for protecting information technology interfaces, in particular telecommunica-
        922 220   4013364433953  04 02 07 03   74 g
              112,00 €   tion connections up to VVDSL and G.fast (up to 1 Gbit/s). Connection of one pair without tools and integrated strain relief for the connecting
                         cable. Connection of a pair or a patch cable with RJ45 plug at the output.
                          Type DBX ...                        TC B 180
                          Part No.                            922 220 +
                          SPD class                           L
                          Max. continuous operating voltage (d.c.)  (UC)  180 V
                          D1 Total lightning impulse current (10/350 µs)  ( Iimp)  7.5 kA
        1              1‘
                          C2 Total nominal discharge current (8/20 µs)  ( In)  20 kA
        2              2‘
                        protected  Series resistance per line   0 ohms
                       4‘
                          Approvals                           EAC
                       5‘
        SI             SI
        SD             SD


                         DBX TC 180
        922 210   DBX TC 180
                         Compact combined arrester in a surface-mounted plastic enclosure for protecting information technology interfaces, particularly telecommu-
           922 210   4013364158214
           04 02 07 03     138   nication connections and devices such as analogue telephones, ISDN and xDSL (VDSL2-tested). Fast connection of one pair without tools and
           g
           118,60 €
                         possibility of strain relief for the connecting cable by means of a cable tie (not included in delivery). Cut-off frequency up to 250 MHz ensures
                         maximum transmission performance in case of high-frequency signal parts.
                          Type DBX ...                        TC 180
                          Part No.                            922 210 (
                          SPD class                           L
                          Max. continuous operating voltage (d.c.)  (UC)  180 V
                          Nominal current at 45°C  (IL)       0.75 A
                          D1 Total lightning impulse current (10/350 µs)  ( Iimp)  7.5 kA
                          C2 Total nominal discharge current (8/20 µs)  ( In)  15 kA
                      1‘
        1
                      protected
                          Series resistance per line          1.8 ohms
        2             2‘
                          Cut-off frequency line-line (100 ohms)  (fG)  250 MHz
                          Dimensions  (L x W x H)             93 x 93 x 55 mm
                          Approvals                           EAC
                         DBX U4 KT BD S 0-180
        922 400   DBX U4 KT BD S 0-180
                         Compact combined lightning current and surge arrester in a surface-mounted plastic enclosure with actiVsense technology for protecting two
        922 400   4013364137349  04 02 07 03   220 g
              205,90 €   pairs with the same or a different signal voltage of galvanically isolated balanced interfaces. The actiVsense technology automatically detects
                         the operating voltage and optimally adapts the voltage protection level to it.
                          Type DBX ...                        U4 KT BD S 0-180
                          Part No.                            922 400
                                                              M
                          SPD class
   SPDs for   Building Systems  2b  2b  Max. continuous operating voltage (d.c.)  (UC)  180 V
                                                              ≤ +/- 5 V
                          Permissible superimposed signal voltage  (Usignal)
                                                              50 MHz
                          Cut-off frequency line-line (Usignal, balanced 100 ohms)  (fG)
                          Nominal current IL (equals max. short-circuit current)  100 mA
        2a            2a
                      protected  D1 Total lightning impulse current (10/350 µs)  ( Iimp)  10 kA
        1b            1b
                          C2 Total nominal discharge current (8/20 µs)  ( In)  20 kA
                          Series resistance per line          ≤ 9 ohms; typically 7.9 ohms
        1a            1a
        9             9
                          Dimensions  (L x W x H)             93 x 93 x 55 mm
         S            S
                          Approvals                           EAC
                          250 V
                             Up
                                                                  C2
                          200 V
                                                                  C3
                                                                  U N
                          150 V
                          100 V
                                                Up   line-line for In (8/20 µs) C2
                           50 V
                                                Up   line-line at 1 kV/µs C3
                                                                UN
                            0 V  20 V  40 V  60 V  80 V  100 V  120 V  140 V  160 V  180 V
                                           Operating voltage U N
                         Voltage protection level diagram (DBX U4 KT BD S 0-180)



        220              You will find detailed product information on our website             Valid as of August 1, 2020