Coordinated Lightning Current Arresters – Type 1
                                                                                                 WBF
                                                                                                DEHN-FUNKENSTRECKEN-TECHNOLOGIE INSIDE
                                                                                                WELLENBRECHER-FUNKTION
        DEHNbloc modular
                                                             • Coordinated spark-gap-based lightning current arrester
                                                               consisting of a base part and a plug-in protection module
                                                             • Maximum system availability due to RADAX Flow follow
                                                               current limitation
                                                             • No tripping of 32 A gG fuses up to short-circuit currents
                                                               of 50 kArms
                                                             • Discharge capacity up to 50 kA (10/350 µs)
                                                             • Directly coordinated with DEHNguard surge protective devices
                                                               without additional cable length
                                                             • Low voltage protection level
                                                             • Operating state / fault indication by green / red indicator flag
                                                               in the inspection window
                                                             • Easy replacement of protection modules without tools due
        For protecting low-voltage consumer installations against surges and even direct   to module locking system with module release button
        lightning strikes. For installation in conformity with the lightning protection zone
        concept at the boundaries from 0A – 1.


        DEHNbloc M 1 ...:   Coordinated and modular single-pole lightning current arrester with high follow current limitation
    Lightning Current Arresters – Type 1  The modular devices of the DEHNbloc M product family are coordinated   The modular design of the DEHNbloc M arresters makes them safe and
        DEHNbloc M 1 ... FM:  With remote signalling contact for monitoring device (floating changeover contact)


                                                             easy to use. Their vibration-proof module locking system, for example, is
        lightning current arresters with a functional design.
                                                             unique. Shock or vibration during transport or operation or enormous
        Energy coordination with type 2 surge arresters of the DEHNguard family
                                                             mechanical impulse loads resulting from discharges do not affect the
        is ensured without additional cable lengths or decoupling coils. This is one
        of the most important features of the Red/Line product families.
                                                             and protection module. Nevertheless, the protection modules can be eas-
        The DEHNbloc M arresters combine high performance and ease of use in   module locking system which ensures safe fixation both for the base part
                                                             ily replaced without tools by simply pressing the easy-to-use module re-
        a single device. Their electrical parameters are rated for the most stringent   lease button. Both the base part and protection module are mechanically
        requirements within lightning and surge protection systems. DEHNbloc M   coded to avoid installing an incorrect module. DEHNbloc M devices incor-
        is ideally suited for use in the main distribution board of the low-voltage   porate double terminals, allowing series connection of the arresters in a
        consumer´s installation of a building. Equipped with the latest RADAX   space-saving and cost-effective way according to IEC 60364-5-53 require-
        Flow spark gap technology, the protection and availability of electrical   ments for nominal currents up to 125 A.
        installations is a top priority of DEHNbloc M.
        Due to the unique follow current limitation and extinction, fuses are not   The operating state / fault indicator of DEHNbloc M does not cause oper-
                                                             ating currents and instantly shows the operating state of the device. Apart
        tripped by follow currents even in case of low-current-rated fuses in the   from the standard visual indicator with red and green indicator flags,
        installation. The leakage-current-free protective circuit and the mechani-  DEHNbloc M ... FM devices feature an additional remote signalling output.
        cal operating state indicator allow the device to be installed even in areas   As the remote signalling contact is designed as a floating changeover
        upstream of meter panels in low-voltage consumer installations.   contact, the remote signal can, depending on the circuit concept, be used
                                                             as a make or break contact.
        961 110   DB M 1 150
        961 120   DB M 1 255  DEHNbloc M 1 ...
        961 130   DB M 1 320
                         Coordinated and modular single-pole lightning current arrester with a high discharge capacity.
        961 110   4013364118560  04 01 01 08   317 g
              253,70 €
        961 120   4013364118614  04 01 01 08   340 g
              263,30 €
        961 130   4013364118638  04 01 01 08   325 g
                          Type DB M 1 ...                   150              255              320
              266,60 €
                          Part No.                          961 110          961 120          961 130
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 / class I   type 1 / class I   type 1 / class I
                          Max. continuous operating voltage (a.c.)  (UC)  150 V (50 / 60 Hz)   255 V (50 / 60 Hz)   320 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs)  (Iimp)  35 kA  50 kA         25 kA
                          Voltage protection level  (UP)    ≤ 1.5 kV         ≤ 2.5 kV         ≤ 2.5 kV
                          Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s)  —  500 A gG  315 A gG
                          Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 5 s)  —  315 A gG    315 A gG
                          Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 0.2 s)  500 A gG  —  —
                          Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 5 s)  315 A gG  —    —
                          Approvals                         UL, CSA          VDE, KEMA, UL    UL
        961 115   DB M 1 150 FM
        961 125   DB M 1 255 FM
        961 135   DB M 1 320 FM  DEHNbloc M  1 ... FM
                         Coordinated and modular single-pole lightning current arrester with a high discharge capacity;
        961 115   4013364118577  04 01 01 08   321 g
              278,20 €   with remote signalling contact for monitoring system (floating changeover contact).
        961 125   4013364118621  04 01 01 08   343 g
              287,90 €
        961 135   4013364118645  04 01 01 08   330 g
              291,10 €
                          Type DB M 1 ...                   150 FM           255 FM           320 FM
                          Part No.                          961 115          961 125          961 135
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 / class I   type 1 / class I   type 1 / class I
                          Max. continuous operating voltage (a.c.)  (UC)  150 V (50 / 60 Hz)   255 V (50 / 60 Hz)   320 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs)  (Iimp)  35 kA  50 kA         25 kA
                          Voltage protection level  (UP)    ≤ 1.5 kV         ≤ 2.5 kV         ≤ 2.5 kV
                          Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s)  —  500 A gG  315 A gG
                          Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 5 s)  —  315 A gG    315 A gG
                          Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 0.2 s)  500 A gG  —  —
                          Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 5 s)  315 A gG  —    —
                          Approvals                         UL, CSA          VDE, KEMA, UL    UL