Combined Arresters – Type 1 + Type 2

                         DEHNshield TT Basic FM
        941 316   DSH B TT 255 FM
                         Application-optimised and prewired combined lightning current and surge arrester for TT and TN-S systems for use in the main power supply
        941 316   4013364328075  04 01 01 04      450 g
              422,20 €   system (3+1 configuration) in case of residential buildings without external lightning protection system (also in case of buildings supplied by
                         overhead lines); with floating remote signalling contact.
                          Type DSH ...                           B TT 255 FM
                          Part No.                               941 316
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE]  (Itotal)  30 kA
    Combined Arresters – Type 1 + Type 2  Max. mains-side overcurrent protection  160 A gG
                                                                 7.5 / 30 kA
                          Lightning impulse current (10/350 µs) [L-N]/[N-PE]  (Iimp)
                          Voltage protection level [L-N]/[N-PE]  (UP)
                                                                 ≤ 1.5 / ≤ 1.5 kV
                                                                 VDE
                          Approvals
                                                                 changeover contact
                          Type of remote signalling contact
                          Extended technical data:
                          Voltage protection level [L-PE]  (UP)
                                                                 2.0 kV

                         DEHNshield TN
        941 200   DSH TN 255
                         Application-optimised and prewired combined lightning current and surge arrester for single-phase TN systems with a nominal voltage of
        941 200   4013364138209  04 01 01 04      250 g
              295,30 €   230 V (2+0 configuration).
                          Type DSH ...                           TN 255
                          Part No.                               941 200
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L+N-PE]  (Itotal)  25 kA
                          Lightning impulse current (10/350 µs) [L, N-PE]  (Iimp)  12.5 kA
                          Voltage protection level [L-PE]/[N-PE]  (UP)  ≤ 1.5 /≤ 1.5  kV
                          Max. mains-side overcurrent protection  160 A gG
                          Approvals                              KEMA, VDE, UL



                         DEHNshield TN FM
        941 205   DSH TN 255 FM
                         Application-optimised and prewired combined lightning current and surge arrester for single-phase TN systems with a nominal voltage of
        941 205   4013364289185  04 01 01 04      260 g   230 V (2+0 configuration); with floating remote signalling contact.
              322,00 €
                          Type DSH ...                           TN 255 FM
                          Part No.                               941 205
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L+N-PE]  (Itotal)  25 kA
                          Lightning impulse current (10/350 µs) [L, N-PE]  (Iimp)  12.5 kA
                          Voltage protection level [L-PE]/[N-PE]  (UP)  ≤ 1.5 /≤ 1.5  kV
                          Max. mains-side overcurrent protection  160 A gG
                          Approvals                              KEMA, VDE
                          Type of remote signalling contact      changeover contact


                         DEHNshield TN Basic FM
        941 206   DSH B TN 255 FM
                         Application-optimised and prewired combined lightning current and surge arrester for single-phase TN systems for use in the main power
        941 206   4013364373839  04 01 01 04      260 g
              209,80 €   supply system (2+0 configuration) in case of residential buildings without external lightning protection system (also in case of buildings
                         supplied by overhead lines); with floating remote signalling contact.
                          Type DSH ...                           B TN 255 FM
                          Part No.                               941 206
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 + type 2 / class I + class II
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs) [L+N-PE]  (Itotal)  15 kA
                          Lightning impulse current (10/350 µs) [L, N-PE]  (Iimp)  7.5 kA
                          Voltage protection level [L-PE]/[N-PE]  (UP)  ≤ 1.5 /≤ 1.5  kV
                          Max. mains-side overcurrent protection  160 A gG
                          Type of remote signalling contact      changeover contact