Coordinated Lightning Current Arresters – Type 1
                                                                                                           WBF
                                                                                                          DEHN-FUNKENSTRECKEN-TECHNOLOGIE INSIDE
                                                                                                          WELLENBRECHER-FUNKTION
           Protection Module for DEHNbloc modular
           • High discharge capacity due to powerful creepage discharge
            spark gap
           • Maximum system availability due to RADAX Flow follow
            current limitation
           • Easy replacement of protection modules without tools due
            to module locking system with module release button
           • Operating state / fault indication by green / red indicator
            flag in the inspection window
           • The plug-in protection module can be replaced without switch-
            ing off the mains voltage or removing the vertical cover




           DB M MOD ...:  Spark-gap-based protection module     For protecting low-voltage consumer installations against surges and even direct
                                                                lightning strikes. For installation in conformity with the lightning protection zone
                                                                concept at the boundaries from 0A – 1.


           The spark-gap-based protection modules for devices of the DEHNbloc M   As with all modular protective devices, protection modules can be easily
           family incorporate the complete protective circuit including the RADAX   replaced without tools by simply pressing the module release button.
           Flow spark gap and the monitoring circuit for controlling the energy flow.   Avoid additional, short-notice and unplanned maintenance jobs.
           The spark gap monitoring system and the operating state / fault indicator   In multipole protective circuits, we recommend replacing the complete set
           are also housed in the protection module.            of protection modules when one module fails.
           Every protection module is mechanically coded to avoid installing an in-                                   Lightning Current Arresters – Type 1
           correct replacement module.
                                                                                                            961 002  961 001   DB M MOD 150
                                                                                                             DB M MOD 255
                                                                                                            961 003   DB M MOD 320
                                                                                                            961 001   4013364118584  04 01 01 08   173 g
                                                                                                                  231,40 €
                                                                                                            961 002   4013364118591  04 01 01 08   195 g
                                                                                                              961 003          241,00 € 4013364118607  04 01 01 08   180 g
           Type DB M MOD ...                    150             255             320
                                                                                                             244,10 €
           Part No.                             961 001         961 002         961 003
           Max. continuous operating voltage (a.c.)  (UC)  150 V  255 V         320 V
           Lightning impulse current (10/350 µs)  (Iimp)  35 kA  50 kA          25 kA




           DEHNbloc modular for North America

           • High discharge current capacity due to powerful creepage
            discharge spark gap
           • Directly coordinated with DEHNguard MU surge protective
            devices without additional cable length
           • ANSI / UL 1449 – 4  Ed. open type 1 surge protection device
                          th
            (SPD)










           DEHNbloc MU 3PY 208 3W+G R:   Modular lightning current arrester for application in 3 phase Wye 208 Y / 120 V electrical systems
           DEHNbloc MU 3PY 480 3W+G R:  Modular lightning current arrester for application in 3 phase Wye 480 Y / 277 V electrical systems
           DEHNbloc MU … R:        With remote status indicator for monitoring device (Form C / SPDT contact)
           DEHNbloc MU 3PY ... 3W+G                                                                         908 505  908 506   DB MU 3PY 208 3W+G R
                                                                                                             DB MU 3PY 480 3W+G R
           DIN rail mount, pluggable lightning current arrester consisting of a base part and plug-in protection modules for application in 3 Phase Wye
           electrical systems.                                                                              908 505    908 506          4013364228139  04 01 01 15   861 g  882 g
                                                                                                             996,80 €
                                                                                                             4013364228146  04 01 01 15
                                                                                                             963,70 €
           Type DB MU 3PY ...                   208 3W+G R              480 3W+G R
           Part No.                             908 505                 908 506
           SPD classification acc. to ANSI/UL 1449 4  Ed.  Open-Type 1 SPD    Open-Type 1 SPD
                                   th
           Max. continuous operating voltage [L-G] / [L-L]  (MCOV)  150 V a.c. / 260 V a.c.   320 V a.c. / 555 V a.c.
           Lightning impulse current (10x350 µs)  (Iimp)  35 kA         25 kA
           Voltage protection rating [L-G] / [L-L]  (VPR)  1500 Vpk / 2500 Vpk   1800 Vpk / 3000 Vpk
           Approvals                            UL                      UL
           Remote status contact                Floating (dry), Form C (SPDT)   Floating (dry), Form C (SPDT)