Combined Arrester – Type 1 + Type 2 for Use in PV Systems
DEHNcombo
• Prewired type 1 + type 2 combined lightning current and surge
arrester for use in photovoltaic generator circuits
• Approved fault-resistant Y circuit prevents damage to the
surge protective device in case of insulation faults in the
generator circuit
• Rated voltage is the same for all modes of protection and,
therefore, the arrester can also be used in earthed systems
Combined Arresters – Type 1 + Type 2 For protecting photovoltaic inverters against surges and even direct lightning • Tested to IEC 61643-31 / EN 61643-31 / EN 50539-11
• Space-saving enclosure with a width of only four modules
for up to 1500 V d.c.
• Applicable in PV systems in accordance with IEC 60364-7-712
• Operating state / fault indication by green / red indicator flag
in the inspection window
strikes. For use in accordance with IEC 60364-7-712 (Installation of photovoltaic
power supply systems).
DEHNcombo DCB YPV 1200: Two-pole combined lightning current and surge arrester for use in photovoltaic power supply systems
up to 1200 V d.c.
DEHNcombo DCB YPV 1500: Two-pole combined lightning current and surge arrester for use in photovoltaic power supply systems
up to 1500 V d.c.
DEHNcombo YPV SCI ... FM: With remote signalling contact for monitoring device (floating changeover contact)
The DEHNcombo YPV ... combined arrester protects equipment in photo- The rated voltage of the new DEHNcombo is the same for all modes of
voltaic systems against lightning currents. protection and, therefore, the arrester can also be used in earthed systems.
Thanks to its application-optimised discharge capacity of 6.25 kA (10/350 1200 V and 1500 V versions are available, covering the most common
µs) per pole, DEHNcombo is tailored to meet the requirements of the voltage levels of photovoltaic systems.
latest version of the EN 50539-12 standard and Supplement 5 of the The fault-resistant Y circuit further reduces the probability of an arrester
German DIN EN 62305-3 standard. failure in case of the operating and fault states which have to be consid-
With a short-circuit current rating of 10 kA, DEHNcombo easily meets all ered in photovoltaic systems. This ensures reliable operation of the PV
requirements placed on surge arresters in small, medium and large pho- system at all times.
tovoltaic systems and can be used without backup fuse in all photovolta- An important requirement in PV systems is the low power consumption
ic systems up to 10 kA. of the devices. A criterium which is met by the current free operating state
Due to its enclosure design which is specifically adapted to the sys- and fault indication, which instantly provides information on the operat-
tem-specific requirements, even the version for voltages up to 1500 V can ing state of the arrester. The optional remote signalling contact is designed
be used without taking special precautions (e.g. safety distances). The as a floating changeover contact and can, depending on the circuit con-
combined arrester has a width of only four modules, thus allowing cept, be used as a make or break contact.
space-saving installation.
DEHNcombo YPV ...
900 070 DCB YPV 1200
900 071 DCB YPV 1500
Combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1500 V d.c.
900 070 6942299504521 04 01 01 05 509 g
223,50 €
Type DCB YPV ... 1200 1500
900 071 6942299504545 04 01 01 05 562 g
268,80 €
Part No. 900 070 + 900 071 +
SPD according to EN 50539-11 type 1 + type 2 type 1 + type 2
Max. PV voltage [DC+ -> DC-] (UCPV) ≤ 1200 V ≤ 1500 V
Short-circuit current rating (ISCPV) 10 kA 10 kA
Total discharge current (10/350 µs) [DC+/DC- -> PE] (Itotal) 12.5 kA 12.5 kA
Lightning impulse current (10/350 µs) [DC+ -> PE/DC- -> PE] (Iimp) 6.25 kA 6.25 kA
Voltage protection level [(DC+/DC-) -> PE] (UP) < 3.8 kV < 4.5 kV
Approvals KEMA, UL KEMA, UL
DEHNcombo YPV ... FM
900 075 DCB YPV 1200 FM
900 076 DCB YPV 1500 FM
Combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1500 V d.c.;
900 075 6942299504538 04 01 01 05 511 g
262,70 € with floating remote signalling contact.
900 076 6942299504552 04 01 01 05 564 g
308,00 €
Type DCB YPV ... 1200 FM 1500 FM
Part No. 900 075 + 900 076 +
SPD according to EN 50539-11 type 1 + type 2 type 1 + type 2
Max. PV voltage [DC+ -> DC-] (UCPV) ≤ 1200 V ≤ 1500 V
Short-circuit current rating (ISCPV) 10 kA 10 kA
Total discharge current (10/350 µs) [DC+/DC- -> PE] (Itotal) 12.5 kA 12.5 kA
Lightning impulse current (10/350 µs) [DC+ -> PE/DC- -> PE] (Iimp) 6.25 kA 6.25 kA
Voltage protection level [(DC+/DC-) -> PE] (UP) < 3.8 kV < 4.5 kV
Approvals KEMA, UL KEMA, UL
Type of remote signalling contact Changeover contact Changeover contact