Combined Arrester – Type 1 + Type 2 for Use in PV Systems


        DEHNcombo
                                                             • Prewired type 1 + type 2 combined lightning current and surge
                                                               arrester for use in photovoltaic generator circuits
                                                             • Approved fault-resistant Y circuit prevents damage to the
                                                               surge protective device in case of insulation faults in the
                                                               generator circuit
                                                             • Rated voltage is the same for all modes of protection and,
                                                               therefore, the arrester can also be used in earthed systems
    Combined Arresters – Type 1 + Type 2  For protecting photovoltaic inverters against surges and even direct lightning   • Tested to IEC 61643-31 / EN 61643-31 / EN 50539-11
                                                             • Space-saving enclosure with a width of only four modules
                                                               for up to 1500 V d.c.

                                                             • Applicable in PV systems in accordance with IEC 60364-7-712
                                                             • Operating state / fault indication by green / red indicator flag
                                                               in the inspection window

        strikes. For use in accordance with IEC 60364-7-712 (Installation of photovoltaic
        power supply systems).


        DEHNcombo DCB YPV 1200: Two-pole combined lightning current and surge arrester for use in photovoltaic power supply systems
                             up to 1200 V d.c.
        DEHNcombo DCB YPV 1500: Two-pole combined lightning current and surge arrester for use in photovoltaic power supply systems
                             up to 1500 V d.c.
        DEHNcombo YPV SCI ... FM: With remote signalling contact for monitoring device (floating changeover contact)

        The DEHNcombo YPV ... combined arrester protects equipment in photo-  The rated voltage of the new DEHNcombo is the same for all modes of
        voltaic systems against lightning currents.          protection and, therefore, the arrester can also be used in earthed systems.
        Thanks to its application-optimised discharge capacity of 6.25 kA (10/350   1200 V and 1500 V versions are available, covering the most common
        µs) per pole, DEHNcombo is tailored to meet the requirements of the   voltage levels of photovoltaic systems.
        latest version of the EN 50539-12 standard and Supplement 5 of the   The fault-resistant Y circuit further reduces the probability of an arrester
        German DIN EN 62305-3 standard.                      failure in case of the operating and fault states which have to be consid-
        With a short-circuit current rating of 10 kA, DEHNcombo easily meets all   ered in photovoltaic systems. This ensures reliable operation of the PV
        requirements placed on surge arresters in small, medium and large pho-  system at all times.
        tovoltaic systems and can be used without backup fuse in all photovolta-  An important requirement in PV systems is the low power consumption
        ic systems up to 10 kA.                              of the devices. A criterium which is met by the current free operating state
        Due to its enclosure design which is specifically adapted to the sys-  and fault indication, which instantly provides information on the operat-
        tem-specific requirements, even the version for voltages up to 1500 V can   ing state of the arrester. The optional remote signalling contact is designed
        be used without taking special precautions (e.g. safety distances). The   as a floating changeover contact and can, depending on the circuit con-
        combined  arrester  has  a  width  of  only  four  modules,  thus  allowing   cept, be used as a make or break contact.
        space-saving installation.


                         DEHNcombo YPV ...
        900 070   DCB YPV 1200
        900 071   DCB YPV 1500
                         Combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1500 V d.c.
        900 070   6942299504521  04 01 01 05   509 g
              223,50 €
                          Type DCB YPV ...                          1200                 1500
        900 071   6942299504545  04 01 01 05   562 g
              268,80 €
                          Part No.                                  900 070 +            900 071 +
                          SPD according to EN 50539-11              type 1 + type 2      type 1 + type 2
                          Max. PV voltage [DC+ -> DC-]  (UCPV)      ≤ 1200 V             ≤ 1500 V
                          Short-circuit current rating  (ISCPV)     10 kA                10 kA
                          Total discharge current (10/350 µs) [DC+/DC- -> PE]  (Itotal)  12.5 kA  12.5 kA
                          Lightning impulse current (10/350 µs) [DC+ -> PE/DC- -> PE]  (Iimp)  6.25 kA  6.25 kA
                          Voltage protection level  [(DC+/DC-) -> PE]  (UP)  < 3.8 kV    < 4.5 kV
                          Approvals                                 KEMA, UL             KEMA, UL
                         DEHNcombo YPV ... FM
        900 075   DCB YPV 1200 FM
        900 076   DCB YPV 1500 FM
                         Combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1500 V d.c.;
        900 075   6942299504538  04 01 01 05   511 g
              262,70 €   with floating remote signalling contact.
        900 076   6942299504552  04 01 01 05   564 g
              308,00 €
                          Type DCB YPV ...                          1200 FM              1500 FM
                          Part No.                                  900 075 +            900 076 +
                          SPD according to EN 50539-11              type 1 + type 2      type 1 + type 2
                          Max. PV voltage [DC+ -> DC-]  (UCPV)      ≤ 1200 V             ≤ 1500 V
                          Short-circuit current rating  (ISCPV)     10 kA                10 kA
                          Total discharge current (10/350 µs) [DC+/DC- -> PE]  (Itotal)  12.5 kA  12.5 kA
                          Lightning impulse current (10/350 µs) [DC+ -> PE/DC- -> PE]  (Iimp)  6.25 kA  6.25 kA
                          Voltage protection level  [(DC+/DC-) -> PE]  (UP)  < 3.8 kV    < 4.5 kV
                          Approvals                                 KEMA, UL             KEMA, UL
                          Type of remote signalling contact         Changeover contact   Changeover contact