Page 83 - Surge-Protection-E_0.pdf
P. 83
Surge Arresters – Type 2
DEHNcord L 2P SN1860 999 937 DCOR L 2P SN1860
Surge arrester for all installation systems; compact design. With disconnection of the load circuit in the event of a fault.
999 937 4013364303195 04 01 02 05 56 g
54,20 €
Type DCOR L 2P SN1860
Part No. 999 937
SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC) 275 V (50 / 60 Hz)
160 30.3 19.4
Nominal discharge current (8/20 µs) (In) 5 kA
Max. discharge current (8/20 µs) (Imax) 10 kA 62.8 67
Voltage protection level [L-N] (UP) ≤ 1.5 kV
Voltage protection level [N-PE] (UP) ≤ 1.5 kV
Max. mains-side overcurrent protection B 16 A
L‘ L N PE
DEHNcord L 2P 275 SO LTG 900 446 DCOR L 2P 275 SO LTG
Surge arrester for all installation systems; compact design. With disconnection of the load circuit in the event of a fault.
900 446 4013364292970 04 01 02 05 49 g
52,40 €
Type DCOR L 2P 275 SO LTG
Part No. 900 446
SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II 60 30.3 19.4
Max. continuous operating voltage (a.c.) [L-N] (UC) 275 V (50 / 60 Hz) 62.8 67
Nominal discharge current (8/20 µs) (In) 5 kA
Max. discharge current (8/20 µs) (Imax) 10 kA
Voltage protection level [L-N] (UP) ≤ 1.5 kV
Voltage protection level [N-PE] (UP) ≤ 1.5 kV
Max. mains-side overcurrent protection B 16 A
Approvals KEMA
L‘ L N PE
DEHNcord L 3P 275 SO LTG 900 445 DCOR L 3P 275 SO LTG
Three-pole surge arrester for all installation systems; compact design.
With disconnection of the load circuit in the event of a fault and protection of the control phase. 900 445 4013364280380 04 01 02 05 58 g
63,50 €
Type DCOR L 3P 275 SO LTG
Part No. 900 445 60 30.3 19.4
SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC) 275 V (50 / 60 Hz) 62.8 67
Nominal discharge current (8/20 µs) (In) 5 kA
Max. discharge current (8/20 µs) (Imax) 10 kA
Voltage protection level [L-N] (UP) ≤ 1.5 kV
Voltage protection level [N-PE] (UP) ≤ 1.5 kV
Max. mains-side overcurrent protection B 16 A
Surge Arresters – Type 2
Approvals KEMA L‘ L L ST N PE
SK EK480 G2S-2d LM DCOR 900 443 SK EK480 G2S-2d LM DCOR
The EK480 fuse box is a high-quality product from Langmatz which stands out for its excellent workmanship and tried and tested features.
The EK480 series meets all mechanical and electrical requirements and standards. This ensures the effective protection of luminaires with 900 443 4013364394322 04 01 02 05 785 g
124,70 €
high-quality electronics against surges resulting from switching operations or nearby lightning strikes.
Type SK EK480 G2S-2d LM DCOR
Part No. 900 443 +
Data of fuse box
Dimensions 276 x 81 x 70 mm
For masts with an inside diameter from 89 mm
Clamping technology incoming: sliding clamp technology / outgoing: spring clamp technology
2
Max. cross-section of connectable cable 1 - 3 cables (4 or 5 x 16 mm )
Outgoing terminals max. 2.5 mm 2
Data of DEHNcord L 3P 275 SO LTG surge protective device
SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating a.c. voltage [L-N] (UC) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In) 5 kA
Max. discharge current (8/20 µs) (Imax) 10 kA
Voltage protection level [L-N] (UP) ≤ 1.5 kV
Voltage protection level [N-PE] (UP) ≤ 1.5 kV
Max. mains-side overcurrent protection B 16 A
Valid as of August 1, 2020 You will find detailed product information on our website 79