Page 276 - V16 Catalogue Final
P. 276
LIGHTNING & SURGE PROTECTION
TYPE 1
In
Imax (8/20µsec)
(8/20μsec) Nominal limp 50Hz Voltage Signal
accord. to No.of Discharge (10/350 Prospective Protection Integral C/O
AS1768 Poles current µsec) Fault Rating Level Up Fuse Contact Part No.
MSB
500kA¹⁾ 1P+PEN 50kA 50kA 50kArms ≤ 2.5kV No Yes DBM1255FM
DBM1255FM
TYPE 1 & 2 COMBINED - WITH MEN LINK
MSB
250kA 1P+PEN 25kA 25kA 100kArms ≤ 1.5 kV Yes Yes DVCI1255FM
250kA 1P+PEN 25kA 25kA 25kArms ≤ 1.5kV Yes Yes DVACSP1P255FM
250kA¹⁾ 3P - KIT 25kA 25kA 100kArms ≤ 1.5kV Yes Yes DVCI1255-TNC
250kA¹⁾ 3P+PEN 25kA 25kA 50kArms ≤ 1.5kV No Yes DVMTNC255FM
125kA¹⁾ 3P+PEN 12.5 12.5kA 25kArms ≤ 1.5kV No Yes DSHTNC255FM
DVCI1255FM
TYPE 1 & 2 COMBINED - WITHOUT MEN LINK
MSB
250kA 2P+PE 25kA 25kA 50kArms ≤1.5kV No Yes DVMTT2P255FM
125kA 2P+PE 12.5kA 12.5kA 25kArms ≤1.5kV No Yes DSHTT2P255FM
250kA 4P-KIT 25kA 25kA 100kArms ≤ 1.5 kV Yes Yes DVCI1255-TT
250kA¹⁾ 4P+PE 25kA 25kA 50kArms ≤ 1.5kV No Yes DVMTT255FM
125kA¹⁾ 4P+PE 12.5kA 12.5kA 25kArms ≤ 1.5kV No Yes DSHTT255FM
DSHTNC255FM
TYPE 2 - WITH MEN LINK
DB
25kA 1P 20kA N/A 25kArms ≤ 1.5 kV Yes No DGSACI275FM
40kA 1P 20kA N/A 50kArms ≤ 1.5kV No No DGS275
N/A 3P+PEN 20kA N/A 25kArms ≤ 1.5kV Yes Yes DGMTNCACI275FM
40kA 3P+PEN 20kA N/A 50kArms ≤ 1.5kV No Yes DGMTNC275FM
50kA 3P+PEN 20kA N/A 25kArms ≤ 2kV No Yes DGMTNC385CNFM
DGS275
TYPE 1 & 2 COMBINED - WITHOUT MEN LINK
DB
25kA 2P+N 20kA N/A 25kArms ≤1.5kV Yes Yes DGMTT2PACI275FM
40kA 2P+PE 20kA 12kA 50kArms ≤1.5kV No Yes DGMTT2P275FM
40kA 1P+N 20kA N/A 25kArms ≤1.5kV No No DGTT2P20340
40kA 4P+PE 20kA L-N N/A 25kArms ≤ 1.5kV Yes Yes DGMTTACI275FM
DGMTT2P275FM 80kA N-PE
40kA¹⁾ 4P+PE 20kA 12kA N-PE 50kArms ≤ 1.5kV No Yes DGMTT275FM
50kA 4P+PE 20kA N/A 25kArms ≤ 2kV No Yes DGMTT385CNFM
40kA 4P+PE 20kA N/A 25kArms ≤1.5kV No No DGTT20340
Final Sub Circuit Surge Filter
20kA 2P+PE 10kA N/A 6kArms ≤1.3kV No Yes SPSPRO27520AFM
1) Refer to AS1768:2007, Section 5.6.3.7, Point III.
SPSPRO27520AFM
268 V16-PV-R04 www.ipd.com.au Phone: 1300 556 601