Page 660 - V16 Catalogue Final
P. 660
SELECTIVITY (DISCRIMINATION)
UPSTREAM – MCCB Tmax XT2 | DOWNSTREAM – MCB S200M (400/415V)
Technology MCCB
PR Tmax XT
Series XT2
Version N,S,H,L,V
Relay EL 160 TM
Technology PR Series Ch. Icu Icu 25 63 100 160 12.5 16 36,50,70,120,150 40 50 63 80 100 125 160
Iu
25
In 10
32
20
0.5..4 T T T T T T T T T T T T T T T T T
6 T T T T 5.5 5.5 5.5 5.5 5.5 5.5 10 T T T T
8 T T T T 5.5 5.5 5.5 5.5 5.5 10 T T T T
10 T T T T 3 3 3 4.5 7.5 7.5 T T T
13 T T T T 3 3 4.5 7.5 7.5 12.5 T T
B,C 16 T T T 3 4.5 5 7.5 12.5 T T
20 T T T 3 5 6 10 T T
25 T T T 5 6 10 10 T
32 40 T T T T T 3 6 7.5 10 T T
7.5
10
10
10
MCB System pro M compact S200M 10 50 63 0.5..4 T T T T T T T T T T T T T T T T T T 10 10
T
T
5.5 5.5 5.5 5.5 5.5 5.5
8 6 T T T T T T T T 5.5 5.5 5.5 5.5 5.5 5.5 T T T T T T T T T T
10 T T T T 3 3 3 3 5 7.5 T T T
13 T T T 2 2 3 6 7.5 T T
D,K 16 T T T 2 2 3 6 7.5 T T
20 T T T 2 3 6 6 T T
25 T T T 3 6 6 T T
32 T T T 4 6 T T
40 T T 7.5 T
50 6 T 5 T
63 T 3 T
652 V16-TR-R03 www.ipd.com.au Phone: 1300 556 601