Page 668 - V16 Catalogue Final
P. 668
BACK-UP (CASCADING)
UPSTREAM – MCCB Tmax XT2 | DOWNSTREAM – DSE S201M (230V)
Technology MCCB
PR Tmax XT
Series XT2
Technology PR Series Ch. Version 16..160 16..160 16..160
N
S
H
Icu
36
70
50
Icu
In
10 50 36 36 40
RCD System pro M compact DSE201M B,C 15 6..10 36 50 70
16..40 36 50 60
UPSTREAM – MCCB Tmax XT4 | DOWNSTREAM – MCB S200 (400/415V)
Technology MCCB
PR Tmax XT
Series XT4
Technology PR Series Ch. Version 80 100 125 36,50,70,85,100 200 225 250 16..250 16..250 16..250
N,S,H,L,V
S
N
H
36
70
Icu
50
Icu
In
160
80 15 15 15 15 15 15 15
B,C 6 15 15 15 15 15 15
MCB System pro M compact S200 100 0.5..10 36 40 40
B,C,D,K,Z 10
13..63 36 40 40