Page 42 - VSD_Brochure_31102023
P. 42
HVAC DRIVES HVAC DRIVES
General software features Take advantage of flexible,
cabinet-free installation
Save space and reduce
overall costs
Maintain process continuity
in harsh conditions
Startup assistant allows first-time users to quickly customise the drive according to their needs.
This is complemented by a built-in help function to make parameter-by-parameter setting easy.
Minimise downtime and
optimise HVAC operation
Motor control is implemented in scalar and vector control modes for induction,
permanent magnet and synchronous reluctance motors. Motor protection
All-in-one drive for wall mounting
features like thermal and overload protection are also established.
The energy optimiser feature optimises the motor flux so that ACH580 WALL MOUNT DRIVES - 0.75kW TO 250kW - IP55
total energy consumption and motor noise level are reduced Features: Standard Duty Light Duty
• Compact, robust and reliable design
when the drive operates below the nominal load. Frame
• Adaptive programming for Output Output Output Output Model Part No.
The total efficiency can be improved by 1…20% Current Power Current Power Size
customisation
(A) (kW) (A) (kW)
depending on load torque and speed. • EMC C2 filter allows safe installation in
first environment Rated Supply Voltage AC (V): 380 - 480, three phases
Energy counter monitors used and saved energy • Integrated safe torque off (STO) 2.6 0.75 2.5 0.75 R1 ACH580-01-02A7-4+B056 3AXD50000038998
function
by the motor and displays it in kWh, currency or 3.3 1.1 3.1 1.1 R1 ACH580-01-03A4-4+B056 3AXD50000038999
• Compliance with the highest safety
CO emissions, to know how much exactly 4 1.5 3.8 1.5 R1 ACH580-01-04A1-4+B056 3AXD50000039000
2 performance level (SIL 3/PL e)
was saved by the drive. • Complete HVAC functionality 5.6 2.2 5.3 2.2 R1 ACH580-01-05A7-4+B056 3AXD50000039001
• Dry clean air-cooling method 7.2 3 6.8 3 R1 ACH580-01-07A3-4+B056 3AXD50000039002
Drive safety and protection features include • Scalar control for effortless process 9.4 4 8.9 4 R1 ACH580-01-09A5-4+B056 3AXD50000039003
control 12.6 5.5 12 5.5 R1 ACH580-01-12A7-4+B056 3AXD50000039004
overcurrent, DC over- and undervoltage, drive
• Vector control for accurate speed and 17 7.5 16.2 7.5 R2 ACH580-01-018A-4+B056 3AXD50000039010
overheating and short circuit protection, motor
torque control
25 11 23.8 11 R2 ACH580-01-026A-4+B056 3AXD50000039011
phase loss and supply phase loss detection, • Extensive I/O connections for flexible
32 15 30.4 15 R3 ACH580-01-033A-4+B056 3AXD50000039012
local control loss detection and many more. configuration
38 18.5 36.1 18.5 R3 ACH580-01-039A-4+B056 3AXD50000039013
45 22 42.8 22 R3 ACH580-01-046A-4+B056 3AXD50000039014
People and machine safety is ensured with drive-
62 30 58 30 R4 ACH580-01-062A-4+B056 3AUA0000083598
based safe-torque-off feature, also allowing to
73 37 68.4 37 R4 ACH580-01-073A-4+B056 3AUA0000083599
conduct maintenance on the mechanical parts of
88 45 82.7 45 R5 ACH580-01-088A-4+B056 3AUA0000083602
equipment without shutting it down.
106 55 100 55 R5 ACH580-01-106A-4+B056 3AUA0000083603
145 75 138 75 R6 ACH580-01-145A-4+B056 3AUA0000083604
Diagnostic assistant helps in locating the cause of 169 90 161 90 R7 ACH580-01-169A-4+B056 3AUA0000083605
any disturbance to the drive, and even suggests 206 110 196 110 R7 ACH580-01-206A-4+B056 3AUA0000083606
possible remedies. This reduces process downtime 246 132 234 132 R8 ACH580-01-246A-4+B056 3AUA0000083607
by making repairs or adjustments effortless. 293 160 278 160 R8 ACH580-01-293A-4+B056 3AUA0000083608
363 200 345 200 R9 ACH580-01-363A-4+B056 3AUA0000083609
A built-in process PID/loop controller 430 250 400 200 R9 ACH580-01-430A-4+B056 3AUA0000083610
makes the drive a self-governing unit that requires - +B056 = Drives with IP55 protection
3AUA0000083604 - +J400 = ACH-AP-H assistant control panel (as standard)
no external logic input from the control room but requires
only an external process measurement.
DIMENSIONS AND WEIGHTS
Backup and restore feature makes automatic and manual
backups of the drive settings to the assistant panel. Frame H W D Weight
Size (mm) (mm) (mm) (kg)
A backup can be restored to another drive.
R1 403 128 233 4.8
R2 503 128 239 6.8
Adaptive programming provides extra flexibility by offering H
R3 490 206 237 13
easy alternative for simple programming needs. Download Drive
R4 636 203 265 20
Composer entry for free to start writing your application.
R5 732 203 320 29
R6 727 252 380 43
D
R7 880 284 381 56
W
R8 965 300 452 77
R9 955 380 477 103
- H = Height of the drive with gland box
- W = Width
- D = Standard depth
42 | Variable Speed Drives Variable Speed Drives | 43