ABB | SACE Tmax XT

                       Connections For references about the connection and terminals, please consult document 1SdM000068r0001; a cable
                                    of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
                                    bus.
                                    To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SdH002009A1503.


                      Power supply Ekip Com Profinet is supplied directly by the Ekip Supply module to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply



                          Interface the module has three signaling leds:

                                                             2                          1










                                    Figure 36

                                     LEDs         Description
                                                  Signals the on status and correct communication with Ekip Touch:
                                                   • off: module off
                                                   • on steady or flashing synchronized with the Power led of Ekip Touch: module on
                                     Power
                                                  and communication with Trip unit present
                                                   • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
                                                  second): module on and communication with Trip unit absent.
                                                  Indicates the communication state:
                                     Link (1)      • off: incorrect connection, signal absent.
                                                   • on steady: connection correct
                                                  Indicates the communication state:
                                     Activity (2)   • off: no activity on line
                                                   • flashing: activity on line present (receiving and/or transmitting)




            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 29).
                                    The following information will be available in the About-Modules menu if Ekip Touch has detected the
                                    module correctly:
                                     Information  Description
                                     SN and version Identifier and SW version of the module
                                                  Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
                                     MAC address
                                                  ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device























       138 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                  External electronic accessories | 8 - Ekip Com Profinet