ABB | SACE Tmax XT

                       Connections
                                    For references about the connection and terminals, please consult document 1SdM000068r0001; a cable
                                    of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
                                    bus.
                                    To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SdH002009A1503.


                      Power supply Ekip Com EtherNet/IP  is supplied directly by the Ekip Supply module to which it is connected.
                                                      TM
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply



                          Interface the module has three signaling leds:

                                                              2                         1










                                    Figure 37

                                     LEDs           Description
                                                    Signals the on status and correct communication with Ekip Touch:
                                                     • off: module off
                                                     • on steady or flashing synchronized with the Power led of Ekip Touch: module
                                     Power
                                                    on and communication with Trip unit present.
                                                     • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
                                                    per second): module on and communication with Trip unit absent
                                                    Indicates the communication state:
                                     Link (1)        • off: incorrect connection, signal absent.
                                                     • on steady: connection correct
                                                    Indicates the communication state:
                                     Activity (2)    • off: no activity on line
                                                     • flashing: activity on line present (receiving and/or transmitting)




            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 29).
                                    The following communication parameters can be configured if the module has been correctly detected by
                                    Ekip Touch in the Settings-Modules menu:

                                     Parameter             Description                                  Default
                                                           Defines whether the module has the dynamic (Off) or
                                     Static IP address ON  static (On) IP address.                      OFF
                                                           Se = On all the associated parameters are enabled
                                     Static address IP address  Enables the static IP to be selected    0.0.0.0
                                     Static Network Mask   Enables the subnet mask to be selected       0.0.0.0
                                                           When there are several subnets, enables the IP address
                                     Static Gateway address  of the node to which the module is connected to be   0.0.0.0
                                                           selected