Page 138 - MCCB-XT2-XT4
P. 138
ABB | SACE Tmax XT
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Parameter for changing the configuration of the module from
Server Only to Client and Server and for integrating it into an
interactive data exchange network (see Ekip Com Hub on page
Client/Server Server only
151)
IMPORTANT: if Client/Server, the module allows data
exchange like a normal Server function
IEEE 1588 Allows the IEEE 1588 protocol for distribution of the clock and
enable synchronization signal to be enabled . OFF
(1)
Master IEEE Enables the module to be set up as a master in the the network OFF
1588 segment to which it belongs (synchronization clock).
IEEE 1588 delay Allows the data exchange mode between module and master, End-to-End
mechanism either Peer-to-Peer or End-to-End, to be selected.
SNTP Client Allows the SNTP protocol for distribution of the clock and OFF
enable synchronization signal to be enabled (1)
Force Static IP Allows the network server that supplies the SNTP to be set. 0.0.0.0
Address
Time zone Defines the time zone to be used for synchronism +00:00
Daylight Saving Used to select whether daylight saving time is present (ON) or OFF
Time not (OFF) in the country to which the synchronization time refers
Permits (Enabled ARP) the periodic generation of a Gratuitous
Disabilita ARP message, used by Ekip Connect to rapidly find the modules ARP Enabled
Gratuitous ARP
via Ethernet scan without knowing the IP address beforehand
Access Enables the writing operations performed via the network to be
protected by protected by a password (Request password) Standard mode
password
Parameter useful if an IEEE 1588 GrandMaster clock is not
available:
• If enabled (ON), the module is seen as an IEEE1588 master
IEEE 1588 clock by all the slaves/devices in the same local network, even
Boundary clock when the source of external synchronism is different from IEEE OFF
1588 (SNTP for example)
• If disabled (OFF) the module benefits from the synchronism of
the master in its own network)
Enable Enables the Rate limiter function, which limits the number of
package packages entering the module from the network, to be activated/ Disable
Limitation deactivated
(1) Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2) the parameter can only be changed via system bus in the remote configuration
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
Boot and HW version General module information
Flash CRC status e
result Information about the correctness of the SW in the module
Stato Ekip Link Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server State of synchronism with SNTP server
Synchronisation
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
IEEE 1588 status Master Active) or absence (PTP Master but Passive) of the higher level
master
136 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 External electronic accessories | 7 - Ekip Com Modbus TCP