Page 138 - MCCB-XT2-XT4
P. 138

ABB | SACE Tmax XT

              Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Parameter    Description                                         Default
                                                  Parameter for changing the configuration of the module from
                                                  Server Only to Client and Server and for integrating it into an
                                                  interactive data exchange network (see Ekip Com Hub on page
                                     Client/Server                                                    Server only
                                                  151)
                                                       IMPORTANT: if Client/Server, the module allows data
                                                     exchange like a normal Server function
                                     IEEE 1588    Allows the IEEE 1588 protocol for distribution of the clock and
                                     enable       synchronization signal to be enabled .              OFF
                                                                               (1)
                                     Master IEEE   Enables the module to be set up as a master in the the network   OFF
                                     1588         segment to which it belongs (synchronization clock).
                                     IEEE 1588 delay  Allows the data exchange mode between module and master,   End-to-End
                                     mechanism    either Peer-to-Peer or End-to-End, to be selected.
                                     SNTP Client   Allows the SNTP protocol for distribution of the clock and   OFF
                                     enable       synchronization signal to be enabled  (1)
                                     Force Static IP   Allows the network server that supplies the SNTP to be set.  0.0.0.0
                                     Address
                                     Time zone    Defines the time zone to be used for synchronism    +00:00
                                     Daylight Saving  Used to select whether daylight saving time is present (ON) or   OFF
                                     Time         not (OFF) in the country to which the synchronization time refers
                                                  Permits (Enabled ARP) the periodic generation of a Gratuitous
                                     Disabilita   ARP message, used by Ekip Connect to rapidly find the modules   ARP Enabled
                                     Gratuitous ARP
                                                  via Ethernet scan without knowing the IP address beforehand
                                     Access       Enables the writing operations performed via the network to be
                                     protected by   protected by a password (Request password)        Standard mode
                                     password
                                                  Parameter useful if an IEEE 1588 GrandMaster clock is not
                                                  available:
                                                   • If enabled (ON), the module is seen as an IEEE1588 master
                                     IEEE 1588    clock by all the slaves/devices in the same local network, even
                                     Boundary clock when the source of external synchronism is different from IEEE   OFF
                                                  1588 (SNTP for example)
                                                   • If disabled (OFF) the module benefits from the synchronism of
                                                  the master in its own network)
                                     Enable       Enables the Rate limiter function, which limits the number of
                                     package      packages entering the module from the network, to be activated/ Disable
                                     Limitation   deactivated

                                    (1)  Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
                                    (2)  the parameter can only be changed via system bus in the remote configuration


                Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Information        Description
                                     Boot and HW version  General module information
                                     Flash CRC status e
                                     result             Information about the correctness of the SW in the module
                                     Stato Ekip Link    Signals Ethernet cable connection errors
                                     SNTP Server Error  Error in communication with SNTP server
                                     SNTP Server        State of synchronism with SNTP server
                                     Synchronisation
                                                        Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
                                     IEEE 1588 status   Master Active) or absence (PTP Master but Passive) of the higher level
                                                        master










       136 | © 2022 ABB |  1SDH002031A1002 - ECN000212994              External electronic accessories | 7 - Ekip Com Modbus TCP