Page 141 - MCCB-XT2-XT4
P. 141
ABB | SACE Tmax XT
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Defines Dataset (acyclic data) access mode
• each individual acyclic register can be accessed in the
Legacy mode using the Slot, Subslot and Index fields (with
Slot fixed at 3)
Data access mode Legacy
• only complete blocks can be accessed in the Dataset
mode; Slot is fixed at 0, Subslot at 1 and Index defines the
block reference
See System Interface for details.
Cyclic data Establishes whether the register of the cyclic data item is Little endian
endianess configured in Big endian or Little endian.
Acyclic data Establishes whether the register of the acyclic data item is
endianess configured in Big endian or Little endian. Big endian
Remote information Certain integrative information concerning the version and state of the module is available via service
connector (via Ekip Connect) or through communication via system bus, i.e.,HW and Boot version, CRC
state (correctness of SW in module), DCP Name, network settings (IP address, Network Mask, Gateway
address)
139 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 External electronic accessories | 8 - Ekip Com Profinet