Page 170 - MCCB-XT2-XT4
P. 170

ABB | SACE Tmax XT

       16 - Ekip CI



                                    Ekip CI is an accessory module configurable with Ekip M Touch, which enables a remote control switch to
                                    be managed in the Normal configuration (page 115).
                                    This module has:
                                     •  a contact for controlling a remote control switch
                                     •  an input for temperature probe PT100 (2 wires)
                                     •  a digital input for the Trip Reset function
                                     •  led for signaling the startup status and operating status of the module
                                    Accessories Ekip Cartridge and Ekip Supply are required in order to connect Ekip Com Hub to Ekip Touch
                                    (page 122, 123).



                       Connections For references about the connection and terminals, please consult document 1SdM000068r0001; for
                                    input I61, use insulated cables for resistance thermometers such as PENTRONIC TEC/SITW-24F (Type TX)
                                    or similar. Maximum length 3 meters. The circuit diagrams are
                                    To connect the module to Ekip Supply and Ekip M Touch, please consult document 1SdH002009A1503.
                                           IMPORTANT: input I61 is not insulated: regardless of plant voltage, the customer must
                                           ensure there is insulation between the input and power supply of the Ekip Supply module
                                           on the basis of the customer's own application and network


                      Power supply Ekip CI is supplied directly by the Ekip Supply module to which it is connected.
                                           NOTE: in the absence of auxiliary power supply, communication between Ekip M Touch and
                                           the module is interrupted, the output contact maintains its status and the input signals are
                                           no longer valid.



                            Output Output contact O61 (K61 and K62), which is normally closed, is opened if a TRIP occurs.
                                    Re-closing can be obtained after a command on the Trip Reset input or if the Autoreclosure function is
                                    active, after the time defined by the user (Autoreclosure Time).
                                    The contact has the following electrical characteristics:
                                     Characteristics                        Maximum limit  (1)
                                     Rated breaking capacity                8A @ 250 VAC / 5A @ 30 VDC
                                     Minimum breaking capacity              10 mA @ 5 VDC
                                     Insulation resistance between contact and Trip   1000 MΩ, 50 VDC
                                     unit

                                    (1) data relating to a resistive load


                        Input PT100 Analog input I61 (H61 and H62) allows a thermocouple to be connected (model PT100) so as to monitor
                                    the temperature and, if PTC protection is activated, to manage a TRIP if an alarm occurs (120 °C fixed
                                    threshold) (page 66)
                                    The contact has the following measuring characteristics:
                                     Input          Measurement     Range           Resolution     Accuracy  (1)
                                     PT100          Temperature     -50 ÷ 250 °C    0,01 °C        ± 0,25 °C  (2)

                                    (1)  accuracy values refer to Ekip CI module without sensor. For complete accuracy, consider the
                                    characteristics of the sensor and cabling used
                                    (2)  accuracy valid in -25 to 250°C range; in complete range it is: ± 0.5 °C














       168 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                         External electronic accessories | 16 - Ekip CI