Page 172 - MCCB-XT2-XT4
P. 172
ABB | SACE Tmax XT
Configuration The module parameters can be configured in the Settings-Modules-Ekip CI menu:
Parameter Description Default
Activates/deactivates certain functions and their availability in
the parameters menu:
Enable • if On: all the inputs, outputs and relative functions are activated Off
• if Off: only input I61 is activated: the command function of O61
is off
Defines whether input I63 is interpreted as On by Ekip Touch
Polarity Active closed
when it is open (Active open) or when it is closed (Active Closed)
Minimum activation time of input I63 before the re-opening
command of contact O61 is sent; the delay is given in seconds
and can be set within range: 0 s to 100 s, in 0.01 s steps
NOTES :
Delay 0.1 s
• if the input is deactivated before this time has elapsed,
the re-opening command is not sent
• if delay = 0 s the input must still be present for longer than
300 µS
Measurements The specific area of the module, containing the temperature measurement of probe PT100 if connected
and activated, will be available in the Measurements menu if Ekip CI is correctly detected by Ekip Touch.
NOTE: value “- - -” will be displayed if no probe is detected
Test The test area in the Test menu is activated if the Ekip CI module is detected correctly.
For details of the test characteristics, please consult page 30.
About If Ekip CI is detected correctly by Ekip Touch, the specific area of the module will be available in the About-
Modules menu, containing:
• the serial number and version of the module
• activation status of the input for temperature probe PT100
Remote information Certain additional information concerning the version and status of the module is available via the service
connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
version, CRC status (correctness of the SW in the module).
170 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 External electronic accessories | 16 - Ekip CI