Page 169 - MCCB-XT2-XT4
P. 169

ABB | SACE Tmax XT

                      Alarm signals Up to three alarm thresholds (independent of each other), Threshold A, Threshold B, Threshold C, can be
                                    activated and configured for each input in the Protection parameters - Other parameters A (and B if dual
                                    set is activated) page
                                    Each alarm threshold has the following configuration parameters:
                                           NOTE: the table lists the parameters of threshold A of input I42; the names and references
                                           of all the other thresholds and inputs change

                                     Parameter          Description                                      Default
                                     Threshold A enable  Activates verification of input I42 with alarm Threshold A  Off
                                                        Defines whether the alarm must activate when measurement
                                     Threshold A hysteresis
                                     direction          is above (Up) or below (Down) the set value, with reference to  Up
                                                        the Threshold A setting
                                                        Alarm threshold A of input I42. The value is given in degrees
                                                        Celsius (°C) and can be set within the range: -40°C to 240°C,  200 °C (I42,
                                                        in 0.1°C steps.                                  I43, I44,
                                     Threshold A value       NOTE: the thresholds of the 4-20 mA (I41 and I51)   I52, I53,
                                                            Current Loop input are given in percentage form and   I54) / 50 %
                                                            can be set within the range: 0% to 100 %, in 0.1% steps  (I41, I51)
                                                            (each step equivalent to 0.016 µA)
                                                        Hysteresis value, valid for quitting the alarm condition if the
                                                        set Treshold A alarm threshold has been exceeded.
                                                        The hysteresis parameter only allows positive values. The trip
                                                        unit decides whether to add or subtract this value to or from
                                                        the alarm threshold on the basis of the direction parameter,   1 °C (I42,
                                                        example:                                         I43, I44,
                                                         • Direction = Up, Value = 200°C, hysteresis= 10°C, the alarm
                                     Threshold A hysteresis                                              I52, I53,
                                                        activates over 200° and de-activates below 190°C
                                                        The value is expressed in degrees Celsius (°C) and can be set   I54) / 1 %
                                                        within the range: 0°C to 50°C with 0.1°C steps.  (I41, I51)
                                                             NOTE: the thresholds associated with the 4-20 mA (I41
                                                            and I51) Current Loop input are given in percentage
                                                            form and can be set within the range 0% to 30 %, in
                                                            0.1% steps (each step equivalent to 0.016 µA)



                  States and alarms The state of all control thresholds can be checked in the Warnings/Alarms page










































       167 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                 External electronic accessories | 15 - Ekip Signalling 3T