Page 171 - MCCB-XT2-XT4
P. 171

ABB | SACE Tmax XT

                    Input Trip reset Digital input I63 (H63 and H64) allows contact O61 to be re-opened after a TRIP.
                                    The module permits two logic statuses, interpreted differently by the Trip unit on the basis of the polarity
                                    configured by the user:
                                                    Electrical condi-               Status detected (and command
                                     State                          Polarity
                                                    tion                            required)
                                                                    Active open     On (O61 open command)
                                     Open           Circuit open  (1)
                                                                    Active closed   Off
                                                                    Active open     Off
                                     Closed         Short-circuit  (2)
                                                                    Active closed   On (O61 open command)

                                    (1)  R > 100 kΩ
                                    (2)  R (wiring + short circuit contact) <25 Ω
                                    The re-closing command is activated at the front.



                          Interface The module has four signaling leds:
                                                                   K K











                                    Figure 44

                                     Parameter      Description
                                                    Signals the on status and correct communication with Ekip Touch:
                                                     • off: module off
                                                     • on steady or flashing synchronized with the Power led of Ekip Touch: module
                                     Power
                                                    on and communication with Trip unit present
                                                     • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
                                                    per second): module on and communication with trip unit absent
                                                    Status of input for temperature probe PT100 I61:
                                                     • off: input disabled
                                     I 61
                                                     • on: input enabled and sensor present
                                                     • flashing: input enabled and sensor disconnected or signal not valid
                                                    Indicates the status of the digital input for Trip Reset I63:
                                     I 63            • off: input open
                                                     • on: input closed
                                                    Indicates the status of the command contact of remote control switch O61:
                                     O 61            • off: contact closed
                                                     • on: contact open




                              Menu Local bus activation, which is essential for starting communication between the module and Trip unit, is
                                    available in the Settings menu (page 29).
                                    The specific configuration, measurement, test and information areas will activate in the respective menus
                                    if the Ekip CI module is detected correctly by Ekip Touch.



















       169 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                         External electronic accessories | 16 - Ekip CI