ABB | SACE Tmax XT
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Preferred If several configuration files are present, allows file hierarchy between .cid
configuration and .iid to be defined .cid
file
Enable IEEE Allows the IEEE 1588 protocol for distribution of the clock and Off
1558 synchronization signal to be enabled .
(1)
IEEE 1558 Enables the module to be set up as a master in the the network segment Off
Master to which it belongs (synchronization clock).
IEEE 1558 Allows the data exchange mode between module and master, either Peer- End-to-
Delay to-Peer or End-to-End, to be selected. End
mechanism
Time zone Defines the time zone to be used for synchronism +00:00
Daylight Used to select whether daylight saving time is present (ON) or not (OFF) in
Saving the country to which the synchronization time refers Off
Time
Defines the file loading procedure:
TFTP • TFTP always On= port open, loading always possible TFTP
Security • TFTP enable required= port normally closed. To start loading, Enable always
level TFTP must be run at the start of the procedure and disable TFTP must be On
run at the end of the procedure (disable not necessary, security command)
Defines the limitations to remote opening and closing command
execution:
CB Open/ • Standard commands= standard commands (unrestricted) activated Standard
CB Close • CB operate request= standard commands not activated. Use commands
command
programmable functions YC COMMAND and YO COMMAND, and Request
breaker open (28) and Request breaker close (29) commands
Zone Analysis of selectivity input from IEC 61850 module can be enabled/ Disabled
Selectivity disabled for each of protections S, S2, G, Gext, D, D(BW), D(FW) (all)
Analysis
Parameter useful if an IEEE 1588 GrandMaster clock is not available:
• If enabled (ON), the module is seen as an IEEE1588 master clock by all
IEEE 1588 the slaves/devices in the same local network, even when the source of
Boundary external synchronism is different from IEEE 1588 (SNTP for example) OFF
clock
• If disabled (OFF) the module benefits from the synchronism of the
master in its own network
Enable Enables the Rate limiter function, which limits the number of packages
package entering the module from the network, to be activated/deactivated Disable
Limitation
(1) Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version General module information
Flash CRC status and result Information about the correctness of the SW in the module
Ekip Link status Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server State of synchronism with SNTP server
Synchronization
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
IEEE 1558 status Master Active) or absence (PTP Master but Passive) of the higher level
master
GOOSE Missing Signals that an expected GOOSE has not been received
Configure Mismatch
Decode Error A GOOSE received does not conform to the expected structure
Sequence number error
Remote programmable
statuses (from E to R) Condition (true/false) of the programmable states and information on
selectivity arising from logic defined in the configuration files loaded
Zone selectivity remote in module IEC 61850
inputs
183 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Internal accessories | 5 - Ekip Com IEC 61850