Page 23 - MCCB-XT2-XT4
P. 23

ABB | SACE Tmax XT

                Programming errors If during the programming of the parameters an attempt is made to violate certain limitations, the trip
                                    unit blocks the saving procedure and signals the error:
                                     Type of error      Error description
                                     30006              Parameter change not completed on display within five minutes
                                     30007              Attempt at remote control with Trip unit configuration in the local mode
                                     30008              Attempt at local control with Trip unit configuration in the remote mode
                                     30011              Error in Ekip Link list of actors
                                                        More than one Time Sync source (IEEE 1588 or SNTP) on one single
                                     30012
                                                        module or between different modules
                                     30013              Network Analyzer parameter control unsuccessful
                                     Active Power Fail  Threshold P23 (protection UP) ≥ Threshold P26 (protection OP)
                                                        Modification of datalogger parameters not allowed with datalogger
                                     DLog not stopped
                                                        function not stopped
                                     D Th ≥ I Th        Threshold I7 (protection D) ≥ Threshold I3 (protection I)
                                     Zone Sel Config = On   Zone selectivity enabling of protection D not allowed with zone selectivity
                                     while S / S2 / I / G = On already active for one among protections S, S2, I or G
                                     G FT time = 50 ms is
                                     not valid          Trip time I4 (protection G) = 50 ms
                                     Gext FT time = 50 ms
                                     isn't valid        Trip time I41 (protection G) = 50 ms
                                     High priority alarm  Modification of parameters not allowed during protection times
                                     I and MCR enabled   Protections I and MCR are mutually exclusive
                                     together
                                     L Th ≥ S Th        Threshold I1 (protection L) ≥ Threshold I2 (protection S)
                                     L Th ≥ S2 Th       Threshold I1 (protection L) ≥ Threshold I5 (protection S2)
                                     L Th > 980 A       Threshold I1 (protetion I) > 980 A with CB in standard configuration UL
                                     Neutral configuration   Configuration of neutral protection must conform to formula: I1 (A) ≥ Iu
                                     error              (A) x Ne config / 100
                                     OV Threshold > 828 V  Threshold U9 (Protection OV) > 828 V (690 x1.2)
                                                        Activation of toroid Rc is not allowed without the presence of a model Rc
                                     RC toroid error
                                                        rating plug
                                     RQ Q24  ≥ Q25      Threshold Q24 ≥ Threshold Q25 (Protection RQ)
                                     S Th ≥  I Th       Threshold I2 (Protection S) ≥ Threshold I3 (Protection I)
                                     S2 Th ≥ I Th       Threshold I5 (Protection S2) ≥ Threshold I3 (Protection I)
                                     S Time > 400 ms    Trip time t2 (protetion S) > 400 ms with CB in standard configuration UL
                                     S2 Time> 400 ms    Trip time t5 (protetion S2) > 400 ms with CB in standard configuration UL
                                     S(V) or S2(V)      Error in configuration of parameters of protection S (V) or S2 (V); consult
                                     parameters         user manual of Trip unit for the limits
                                     SYNCHRO parameters   Inconsistency of Synchrocheck protection parameters: Delta phase ≥ 180
                                     error              x Delta freq x [minimum correspondence time + 0.0023]
                                     V DIR Th > 690*1.2  Protection threshold VDIR > 828 V (690 x1.2)
                                     VS Th > 690*1.2    One of the two thresholds of protection VS Warning > 828 V (690 x1.2)




























       21 | © 2022 ABB |  1SDH002031A1002 - ECN000212994            Management operations | 2 - Maintenance and troubleshooting