Programming errors If during the programming of the parameters an attempt is made to violate certain limitations, the trip
unit blocks the saving procedure and signals the error:
Type of error Error description
30006 Parameter change not completed on display within five minutes
30007 Attempt at remote control with Trip unit configuration in the local mode
30008 Attempt at local control with Trip unit configuration in the remote mode
30011 Error in Ekip Link list of actors
More than one Time Sync source (IEEE 1588 or SNTP) on one single
30012
module or between different modules
30013 Network Analyzer parameter control unsuccessful
Active Power Fail Threshold P23 (protection UP) ≥ Threshold P26 (protection OP)
Modification of datalogger parameters not allowed with datalogger
DLog not stopped
function not stopped
D Th ≥ I Th Threshold I7 (protection D) ≥ Threshold I3 (protection I)
Zone Sel Config = On Zone selectivity enabling of protection D not allowed with zone selectivity
while S / S2 / I / G = On already active for one among protections S, S2, I or G
G FT time = 50 ms is
not valid Trip time I4 (protection G) = 50 ms
Gext FT time = 50 ms
isn't valid Trip time I41 (protection G) = 50 ms
High priority alarm Modification of parameters not allowed during protection times
I and MCR enabled Protections I and MCR are mutually exclusive
together
L Th ≥ S Th Threshold I1 (protection L) ≥ Threshold I2 (protection S)
L Th ≥ S2 Th Threshold I1 (protection L) ≥ Threshold I5 (protection S2)
L Th > 980 A Threshold I1 (protetion I) > 980 A with CB in standard configuration UL
Neutral configuration Configuration of neutral protection must conform to formula: I1 (A) ≥ Iu
error (A) x Ne config / 100
OV Threshold > 828 V Threshold U9 (Protection OV) > 828 V (690 x1.2)
Activation of toroid Rc is not allowed without the presence of a model Rc
RC toroid error
rating plug
RQ Q24 ≥ Q25 Threshold Q24 ≥ Threshold Q25 (Protection RQ)
S Th ≥ I Th Threshold I2 (Protection S) ≥ Threshold I3 (Protection I)
S2 Th ≥ I Th Threshold I5 (Protection S2) ≥ Threshold I3 (Protection I)
S Time > 400 ms Trip time t2 (protetion S) > 400 ms with CB in standard configuration UL
S2 Time> 400 ms Trip time t5 (protetion S2) > 400 ms with CB in standard configuration UL
S(V) or S2(V) Error in configuration of parameters of protection S (V) or S2 (V); consult
parameters user manual of Trip unit for the limits
SYNCHRO parameters Inconsistency of Synchrocheck protection parameters: Delta phase ≥ 180
error x Delta freq x [minimum correspondence time + 0.0023]
V DIR Th > 690*1.2 Protection threshold VDIR > 828 V (690 x1.2)
VS Th > 690*1.2 One of the two thresholds of protection VS Warning > 828 V (690 x1.2)
21 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Management operations | 2 - Maintenance and troubleshooting