ABB | SACE Tmax XT

                       2I Protection Function
                                    If the current of one or more phases exceeds threshold I31 and a trip event is present, the protection
                  t                 transmits the TRIP command after a non-programmable fixed time.
                       I31    2I
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 75)
                                     •  the graph with trip curve (page 83)
                                     Parameter  Description                                             Default
                                  I  Enable     Activates/deactivates the protection and its availability in the   OFF
                                                parameters menu.
                                                Establishes the value that activates the protection.
                                     Threshold   The value is given as both absolute value (A) and relative value (In) and  1,5 In
                                     I31
                                                can be set within the range: 1.5 In to 10 In, in 0.1 In steps
                                                Activates/deactivates the function
                                                     NOTE: if at least two of the selectivity S, S2, I, 2I and MCR are
                                     ZoneSelectivity  enabled, the input and output are shared with the OR function; it  OFF
                                                    is sufficient that even a selectivity is activated to stimulate inputs
                                                    and outputs


                                    Protection enabling renders 2I Mode section available in Advanced - Functions menu, where the protection
                                    activation event can be configured:
                                     Parameter  Description                                             Default
                                                Two alternative modes are available:
                                                 • Dependent function: the protection is activated if the programmed
                                     Activation  activation event has occurred; this configuration makes the function   Dependent
                                                                                                        function
                                                and delay parameters available
                                                 • Activated: the protection is always activated
                                                The activation event between the input contacts of Ekip Signalling 2K,
                                                the statuses of the unit (open/closed) and the Custom function can
                                                be selected
                                     Function                                                           Disabled
                                                    NOTE: Ekip Connect allows the Custom function to be
                                                    customized so as to associate the activation event with up to
                                                    eight statuses in AND or OR configuration
                                                Protection activation delay calculated from the presence of the
                                                activation event onwards.
                                                The value is given in seconds and can be set within range: 0 s to 100 s,
                                     Delay ON                                                           0 s
                                                in 0.01 s steps
                                                    NOTE: the protection trips if the event is present for longer than
                                                    the set time lag
                                                Protection deactivation delay calculated from disappearance of
                                                activation event onwards.
                                                The value is given in seconds and can be set within range: 0 s to 100 s,
                                     Delay OFF                                                          15 s
                                                in 0.01 s steps
                                                    NOTE: protection deactivates if event is not present for longer
                                                    than set delay


                                    RELT - Ekip signalling 2K-3
                                    If the RELT module is present a dedicated command (RELT Wizard) will be displayed. This will program the
                                    2I protection and other related parameters; for details see page 155.
                                    Commands by remote control
                                    Two further temporary protection activation/deactivation commands are available when the unit is
                                    connected to one or more Ekip Com modules:
                                     •  2I ON Mode: activates the protection
                                     •  2I OFF Mode: deactivates the protection
                                    For further details consult the document 1SdH002031A1101.
                                           NOTE: if the protection has been activated by command 2I ON Mode, it is deactivated by
                                           command 2I OFF Mode or when the unit shuts down
                                    Signallings
                                    When protection 2I is activated, the message “2I active” appears in the diagnostic bar and in the Alarm List
                                    page, and the alarm led will be on steady.