                       S Protection Function
                                    If the current of one or more phases exceeds threshold I2, the protection trips and, after a time established
                  t                 by the value read and by the parameter settings, transmits the TRIP command.
                       I2     S     To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  the summary table of the protections with the calculation formulas (page 75)
                            t2       •  the graph with trip curve (page 81)
                                    Parameters
                                  I  Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu.
                                                  Activates/deactivates transmission of the open command. if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   ON
                                                  managed as information.
                                                  Establishes curve dynamics and the threshold or trip time
                                                  calculation:
                                     Curve                                                            t = k
                                                       • t = k: fixed time trip
                                                       • t = k/I : inverse time-delay dynamic trip
                                                              2
                                                  Establishes the value that activates the protection and
                                                  contributes towards calculating the trip time.
                                     Threshold I2                                                     2 In
                                                  The value is given as both absolute value (A) and relative value (In)
                                                  and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                  It is the trip time or contributes towards timing calculation,
                                                  depending on the type of curve selected.
                                     Time t2                                                          0.1 s
                                                  The value is given in seconds and can be set within the range:
                                                  0.05 s to 0.4 s, in 0.01 s steps
                                                  Activates/deactivates the thermal memory function (page 67)
                                     Thermal                                                  2
                                     memory           NOTE:the function is only available with curve t=k/I  OFF

                                                  Activates/deactivates the function and selectivity time availability
                                                  on the display (page 67)
                                     ZoneSelectivity                                                  OFF
                                                      NOTE:the function is only available with curve t=k

                                                  This is the trip time of the protection with the zone selectivity
                                                  function activated and selectivity input not present (page 67)
                                     Selectivity time                                                 0,04 s
                                                  The value is given in seconds and can be set within the range:
                                                  0.04 s to 0.2 s, in 0.01 s steps
                                                  Activates/deactivates the function and availability of the
                                     StartUp enable                                                   OFF
                                                  associated parameters on the display (page 70)
                                                  Protection threshold valid during Startup time, in the conditions
                                     StartUp      in which the function is activated (page 70)
                                     Threshold    The value is given as both absolute value (A) and relative value (In)   0,6 In
                                                  and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                  This is the time for which the StartUp threshold remains
                                                  activated, as calculated from the moment the activation
                                     StartUp Time  Threshold is exceeded (page 70)                    0.1 s
                                                  The value is given in seconds and can be set within the range: 0.1
                                                  s to 30 s, in 0.01 s steps

                                    Limitations and additional functions
                                     •  threshold I2 must be higher than threshold I1 (if S protection is activated)
                                                                2
                                     •  in the presence of curve t= k/I , the protection trip time is forced to t2 if the calculation results
                                       give a theoretical value lower than t2 itself
                                     •  the block functions and type of selectivity can also be accessed by means of the service connector
                                       (via Ekip Connect) or communication via system bus (page 67)
                                     •  with CB in UL standard configuration, the maximum value of t2 is 400 ms














       37 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                               Protections | 2 - Standard Protections