Page 42 - MCCB-XT2-XT4
P. 42

ABB | SACE Tmax XT

                       G Protection Function
                                    Ekip Touch calculates the vector sum of the phase currents (L1, L2, L3, Ne) and obtains the internal earth
                  t                 fault current (Ig): if current Ig exceeds threshold I4, the protection trips and, after a time established by
                       I4     G     the value read and by the parameter settings, transmits the TRIP command.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                            t4       •  the summary table of the protections with the calculation formulas (page 75)
                                     •  the graph with trip curve (page 84)
                                    Parameters
                                  I
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu.
                                                  Activates/deactivates transmission of the open command. if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   ON
                                                  managed as information.
                                                  Establishes curve dynamics and the threshold or trip time
                                                  calculation:
                                     Curve                                                            t = k
                                                       • t = k: fixed time trip
                                                       • t = k/I : inverse time-delay dynamic trip
                                                              2
                                                  Establishes the value that activates the protection and
                                                  contributes towards calculating the trip time.
                                     Threshold I4                                                     0,2 In
                                                  The value is given as both absolute value (A) and relative value (In)
                                                  and can be set within the range: 0.1 In to 1 In, in 0.001 In steps
                                                  It is the trip time or contributes towards timing calculation,
                                                  depending on the type of curve selected.
                                                  The value is given in seconds and can be set within the range: 0.1
                                     Time t4      s to 1 s, in 0.05 s steps                           0.1 s
                                                      NOTE: in the presence of curve: t = k, t4 can also be
                                                     configured as: instantaneous; in this mode, the trip time is
                                                     comparable to that given for I protection (page 75)
                                                  Warns that the measured current is near to the protection
                                                  activation threshold.
                                                  The value is given in percentage of threshold I1 and can be set
                                     Prealarm I4  within the range 50% I4 to 90% I4, in 1% steps.     90 % I4
                                                  The prealarm condition deactivates in two cases:
                                                       • current lower than prealarm threshold I4
                                                       • current higher than threshold I4
                                                  Activates/deactivates the function and selectivity time availability
                                                  on the display (page 67)
                                     ZoneSelectivity                                                  OFF
                                                      NOTE: the function is only available with curve t = k

                                                  This is the trip time of the protection with the zone selectivity
                                                  function activated and selectivity input not present (page 67)
                                     Selectivity time                                                 0,04 s
                                                  The value is given in seconds and can be set within the range:
                                                  0.04 s to 0.2 s, in 0.01 s steps
                                                  Activates/deactivates the function and availability of the
                                     StartUp enable                                                   OFF
                                                  associated parameters on the display (page 70)
                                                  Protection threshold valid during Startup time, in the conditions
                                     StartUp      in which the function is activated (page 70)        0,2 In
                                     Threshold    The value is given as both absolute value (A) and relative value (In)
                                                  and can be set within the range: 0.2 In to 1 In, in 0.02 In steps
                                                  This is the time for which the StartUp threshold remains
                                                  activated, as calculated from the moment the activation
                                     StartUp Time  Threshold is exceeded (page 70)                    0.1 s
                                                  The value is given in seconds and can be set within the range: 0.1
                                                  s to 30 s, in 0.01 s steps


                                                                                                Continued on the next page











       40 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                               Protections | 2 - Standard Protections