                      UP Protection Function
                                    The protection sends a TRIP command if one or more of the active power values detected by the unit drop
                  t                 below threshold P23 for longer than t23.
                              UP
                        P23         The protection is active also for negative (reverse) active power, but is independent from the RP protection
                                    (Reverse active power protection).
                    t23             The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                 P   •  summary table of the protections with the operating characteristics (page 76)
                                     •  the graph with trip curve (page 91)
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (kW) and relative value
                                     Threshold P23                                                    1 Sn
                                                  (Sn) and can be set within the range: 0.1 Sn to 1 Sn in 0.001 Sn
                                                  steps
                                                  This is the trip time of the protection; the value is given in
                                     Time t23     seconds and can be set within a range: 0.5 s to 100 s, in 0.5 s   1 s
                                                  steps
                                                  Activates/deactivates the function and availability of the StartUp
                                     StartUp enable                                                   OFF
                                                  Time parameter in the menu
                                                  This is the time for which the threshold remains disabled and is
                                                  calculated from the moment the activation Threshold is exceeded
                                     StartUp Time                                                     0.1 s
                                                  The value is given in seconds and can be set within the range: 0.1
                                                  s to 30 s, in 0.01 s steps
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 70).


                      RQ Protection Function
                                    RQ protection protects against reactive power reversal; the threshold can be adjusted on the basis of the
                                    active power.
                                    The protection sends a TRIP command when inverse reactive power enters the TRIP area, determined by
                                    the protection parameters and power value readings, for longer than t24.
                                    Adjustment of constants Kq and Kq2 allows the trip threshold of the protection (determined by the
                                    intersection of the two TRIP areas, whose limits depend on the parameters configured in the unit) to be
                                    changed.
                                                         Q




                                                                  Kq2     Kq
                                                                                             P

                                                       Q24         TRIP

                                                       Q25


                                    Figure 21

                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 76)
                                     •  the graph with trip curve (page 91)