Page 57 - MCCB-XT2-XT4
P. 57

ABB | SACE Tmax XT

       6 - Power protections



                               List The Power protections, available by default for the Ekip Hi-Touch and Ekip M Touch models and
                                    configurable in the remaining models as additional SW package, are:
                                     Name       Type of protection                         Page
                                     RP         Reverse active power                       55
                                     D          Directional short-circuit with adjustable delay  56
                                     OQ  (1)    Maximum reactive power                     58
                                     OP  (1)    Active overpower                           58
                                     UP  (1)    Active underpower                          59
                                     RQ  (1)    Reverse reactive power                     59
                                     Cos φ      Minimum Cos φ                              60

                                    (1)  protection not available by default with Ekip Hi-Touch and Ekip M Touch. However, it can be
                                    integrated by requesting the relative SW package

                                           WARNING! The Power flow parameters effect the sign of the power and power factor
                                           values measured by the unit. Power flow must be configured and verified on the basis of
                                           your installation to ensure that all the protections of the Power Protections package
                                           function correctly



                      RP Protection Function
                                    The protection sends a TRIP command if the reverse total active power exceeds threshold P11 for longer
                                t   than t1.
                     RP  P11        To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 76)
                     t11             •  the graph with trip curve (page 89)
                                    Parameters
                                 P   Parameter      Description                                           Default
                                                   Activates/deactivates the protection and its availability in the
                                     Enable                                                               OFF
                                                   parameters menu
                                                   Activates/deactivates transmission of the open command: if
                                     Trip Enable   disabled, the alarm and exceedance of protection time are only   OFF
                                                   managed as information
                                                   Establishes the value that activates the protection.
                                                   The value is given as both absolute value (kW) and relative value (Sn)
                                     Threshold P11  and can be set within the range: -0.05 Sn to -1 Sn in 0.001 Sn steps  0,1 Sn
                                                       NOTE: the threshold expressed in Sn is preceded by the “-” sign
                                                       to indicate that inverse power is involved
                                                   This is the trip time of the protection; the value is given in seconds
                                     Time t11                                                             10 s
                                                   and can be set within a range: 0.05 s to 100 s, in 0.01 s steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 70).





















       55 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                                 Protections | 6 - Power protections