ABB | SACE Tmax XT

                      OQ Protection Function
                                    The protection sends a TRIP command if one or more of the reactive power values detected by the unit
                  t                 exceed threshold Q27 for longer than t27.
                       Q27   OQ     To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 76)
                            t27      •  the graph with trip curve (page 90)
                                    Parameters
                                 Q   Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (kVAR) and relative value
                                     Threshold Q27                                                    1 Sn
                                                  (Sn) and can be set within the range: 0.4 Sn to 2 Sn in 0.001 Sn
                                                  steps
                                                  This is the trip time of the protection; the value is given in
                                     Time t27     seconds and can be set within a range: 0.5 s to 100 s, in 0.5 s   1 s
                                                  steps


                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 70).


                      OP Protection Function
                                    The protection sends a TRIP command if one or more of the active power values detected by the unit
                  t                 exceed threshold P26 for longer than t26.
                       P26   OP     To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 76)
                            t26      •  the graph with trip curve (page 90)
                                    Parameters
                                P    Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information
                                                  Establishes the value that activates the protection.
                                                  The value is given as both absolute value (kW) and relative value
                                     Threshold P26                                                    1 Un
                                                  (Sn) and can be set within the range: 0.4 Sn to 2 Sn in 0.001 Sn
                                                  steps
                                                  This is the trip time of the protection; the value is given in
                                     Time t26     seconds and can be set within a range: 0.5 s to 100 s, in 0.5 s   1 s
                                                  steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 70).